Samsung Electronics 2-45
Indoor Unit(cont.)
QGlobal Duct 2
Model
Global Duct 2
AM024MNMDCH/AA AM027MNMDCH/AA AM030MNMDCH/AA
Power Supply Φ, #, V, Hz 1,2,208-230,60 1,2,208-230,60 1,2,208-230,60
Mode - HP/HR HP/HR HP/HR
Performance
Capacity
(Nominal)
Cooling 2)
kW - - -
Btu/h 24,000 27,000 30,000
Heating 2)
kW---
Btu/h 27,000 30,000 34,000
Condensate
(with high fan speed)
Liter/h - - -
Power
Power Input
(Nominal)
Cooling 1) W 114 125 132
Heating 2) W 114 125 132
Current Input
(Nominal)
Cooling 1) A 0.81 0.87 0.92
Heating 2) A 0.81 0.87 0.92
Fan
Type - Sirocco Fan Sirocco Fan Sirocco Fan
Motor
Model -
Type - BLDC BLDC BLDC
Output x n W 153 x 1 153 x 1 153 x 1
Air Flow Rate H/M/L CMM 22 23 24
External
Pressure
Min / Std / Max
mmAq 3.0 / 5.2 / 20.0 3.0 / 5.2 / 20.0 3.0 / 5.2 / 20.0
Pa 29.4 / 51.0 / 196.1 29.4 / 51.0 / 196.1 29.4 / 51.0 / 196.1
Sound
Sound Pressure High / Mid / Low dB(A) 39 / 36 / 30 40 / 37 / 34 40 / 38 / 35
Sound Power Cooling dB(A) - - -
Refrigerant
Type - R410A R410A R410A
Control Method - EEV INCLUDED EEV INCLUDED EEV INCLUDED
Temperature Control - Micom&Thermistors Micom&Thermistors Micom&Thermistors
Safety Devices - Fuse Fuse Fuse
Piping
Connections
Liquid Pipe (Flare)
Φ,mm 9.52 9.52 9.52
Φ, inch 3/8" 3/8" 3/8"
Gas Pipe (Flare)
Φ,mm 15.88 15.88 15.88
Φ, inch 5/8" 5/8" 5/8"
Drain Pipe (Quick lock) Φ,mm VP25 (OD 32,ID 25) VP25 (OD 32,ID 25) VP25 (OD 32,ID 25)
Dimensions
Net Weight kg 45.2 45.2 45.2
Shipping Weight kg 50.0 50.0 50.0
Net Dimensions (W×H×D) mm 1,200 x 250 x 700 1,200 x 250 x 700 1,200 x 250 x 700
Shipping Dimensions (W×H×D) mm 1,429 x 320 x 779 1,429 x 320 x 779 1,429 x 320 x 779
Funtion
Auto restart - o o o
Auto swing - x x x
Group/Individual control - o o o
Exteral contact control - o o o
Trouble shooting by LED - x x x
Standard
accessories
Installation manual - o o o
Operation manual - o o o
Pattern sheet for installation - x x x
Flexible drain hose - o o o
Flilter/Safety grille - Long life filter Long life filter Long life filter
Drain pump
Drain pump - Built-In Built-In Built-In
Max. lifting Height
/ Displacement
mm / liter/ h
750 / 24 750 / 24 750 / 24
Optional
accessories
Wireless remote controller - MR-DH00U MR-DH00U MR-DH00U
wired remote controller - MWR-WE10N MWR-WE10N MWR-WE10N
External contact interface module - MIM-B14 MIM-B14 MIM-B14
Duct Receiver kits - MRK-A10N MRK-A10N MRK-A10N
EEV kits - - - -
*1) Mode
- HP : Heat Pump, HR : Heat Recovery
*2) Nominal cooling capacities are based on;
- Indoor temperature : 27˚C DB, 19˚C WB
- Outdoor temperature : 35˚C DB, 24˚C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
*3) Nominal heating capacities are based on;
- Indoor temperature : 20˚C DB, 15˚C WB
- Outdoor temperature : 7˚C DB, 6˚C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.