EasyManua.ls Logo

Samsung AM036JNCDCH - Page 24

Samsung AM036JNCDCH
33 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
24
Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6
Explanation
PAGE MODE
Use of Auto Change
Over for HR only in
Auto mode
(When setting SEG3)
Standard heating
temp. Oset
(When setting SEG3)
Standard cooling temp.
Oset
(When setting SEG3)
Standard for mode
change
Heating
Cooling
Remote
Controller
Display
Auto
On
On
Auto
Cool
On
Cool
On
On
Dry
Indication
and Details
Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details
05
0
Follow
product
option
0 0°F(0°C) 0 0°F(0°C) 0 1.8°F(1°C)
1
Use Auto
Change
Over for
HR only
1 0.9°F(0.5°C) 1 0.9°F(0.5°C) 1 2.7°F(1.5°C)
2 1.8°F(1°C) 2 1.8°F(1°C) 2 3.6°F(2°C)
3 2.7°F(1.5°C) 3 2.7°F(1.5°C) 3 4.5°F(2.5°C)
4 3.6°F(2°C) 4 3.6°F(2°C) 4 5.4°F(3°C)
5 4.5°F(2.5°C) 5 4.5°F(2.5°C) 5 6.3°F(3.5°C)
6 5.4°F(3°C) 6 5.4°F(3°C) 6 7.2°F(4°C)
7 6.3°F(3.5°C) 7 6.3°F(3.5°C) 7 8.1°F(4.5°C)
Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
Explanation
PAG E
(When setting SEG3)
Standard for mode
changing Cooling
Heating mode
(When setting SEG3)
Time required for
mode change
Compensation option
for Long pipe or height
diference between
indoor units
Remote
Controller
Display
On
Dry
On
Fan
On
Fan
Indication
and Details
Indication Details Indication Details Indication Details Indication Details
1
0 1.8°F(1°C) 0 5 min. 0
Use default
value
1 2.7°F(1.5°C) 1 7 min.
1
1) Height
difference
1)
is more than
30m or
2) Distance
2)
is longer than
110m
2 3.6°F(2°C) 2 9 min.
3 4.5°F(2.5°C) 3 11 min.
4 5.4°F(3°C) 4 13 min.
2
1) Height
difference
1)
is
15~30m or
2) Distance
2)
is
50~110m
5 6.3°F(3.5°C) 5 15 min.
6 7.2°F(4°C) 6 20 min.
7 8.1°F(4.5°C) 7 30 min.
Q
05 series installation option(Detailed)
Option No. : 05XXXX-1XXXXX-2XXXXX-3XXXXX
Setting an indoor unit address and installation option

Related product manuals