ENGLISH
(*1)
Height dierence : The dierence of the height between the corresponding indoor uint and the indoor unit installed at the lowest place.
For example, When the indoor unit is installed 131.2ft(40m) higher than the indoor unit installed at the lowest place, select
the option "1".
(*2)
Distance : The dierence between the pipe length of the indoor unit istalled at farthest place from an outdoor unit and the pipe length of the
corresponding indoor unit from an outdoor unit.
For example, when the farthest pipe length is 328 ft(100m) and the corresponding indoor unit is 131.2ft(40m) away from an outdoor
unit, select the option "2".
[328-131.2=196.8ft(100 - 40 = 60m)]
(*3) Heater operation when the SEG9 of 02 series installation option is set to using hot water heater or when SEG15 is set to using external heater
e.g. 1) Setting 02 series SEG9 =”1” / Setting 05 series SEG18 = “0”: Hot water heater is turned on at the same time as the heating thermostat
is on, and turned o when the heating thermostat is o.
e.g. 2) Setting 02 series SEG15 =”2” / Setting 05 series SEG18 =”A”:
Room temp. ≤ set temp. + f(heating compensation temp.)
- External heater is turned on when the temperature is maintained as 8.1 °F(4.5 °C) for 10 minutes.
Room temp. > set temp. + f(heating compensation temp.)
- External heater is turned o when the temperature is maintained as 8.1 °F(4.5 °C) + 1.8 °F(1 °C) [1 °C is the Hysteresis for On/O
selection.]
Option SEG13 SEG14 SEG15 SEG16 SEG17
SEG18
(*3)
Explanation
Control variables when using hot water / external heater
Remote
Controller
Display
Off
Dry
Indication
and Details
Indication
Details
Set temp. for heater On/O
Delay time for heater On
2
0 At the same time as thermo on No delay
1
At the same time as thermo on
10 minutes
2 At the same time as thermo on 20 minutes
3 2.7 °F(1.5 °C) No delay
4 2.7 °F(1.5 °C) 10 minutes
5 2.7 °F(1.5 °C) 20 minutes
6 5.4 °F(3.0 °C) No delay
7 5.4 °F(3.0 °C) 10 minutes
8 5.4 °F(3.0 °C) 20 minutes
9 8.1 °F(4.5 °C) No delay
A 8.1 °F(4.5 °C) 10 minutes
B 8.1 °F(4.5 °C) 20 minutes
C 10.8 °F(6.0 °C) No delay
D 10.8 °F(6.0 °C) 10 minutes
E 10.8 °F(6.0 °C) 20 minutes