EasyManua.ls Logo

Samsung AM048FXMDCH - Page 18

Samsung AM048FXMDCH
50 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
17
ENGLISH
Pipe installation for an outdoor unit
Pipe direction
The refrigerant pipe can be pulled out from front,ank, rear, and bottom side, so install it depending on the installation site
condition.
Caution for using knock-out hole
Make sure not to damage the exterior of the outdoor unit.
Remove all burrs at the edge of the knock-out hole and apply the paints it to prevent
rust.
Use a cable tube and bushing to prevent a cable from being damaged when passing
through a knock-out hole.
After installing pipes, block the unused knock hole to prevent small animal from
entering. However, the radiant heat hole (A) should be able to intake air.
CAUTION
Caution for connecting the pipe
When brazing the pipe, the unit may get damaged by a brazingre and a
flame. Use aame proofing cloth to protect the unit from a brazing fire or
flame.
The O-ring and Teflon packing inside service valve may get damaged by a
brazing re. Wrap the bottom side of the service valve with a wet cloth and
braze it as shown above. Make sure not to interrupt the brazing with the
drips from the wet cloth.
The connecting pipes of liquid side and gas side should not contact each
other nor should they contact to the product. Vibration may cause damage
to the pipes.
CAUTION
High pressure
(Liquid side)
Low pressure
(Gas side)
Outdoor unit refrigerant pipe connection
Classification Front,ank, rear side of pipe connection Bottom side of pipe connection
Working process
First, remove the pipe cover from unit.
Separate the knock-out hole to use. If the
hole is open, small animals such as squirrels
and rats may get into the unit through the
hole and the unit may be damaged.
Separate the knock-out hole at the bottom
side of the unit and install the pipe.
After installing and insulating the pipe,
close up the remaining gap. If the gap
remains open, small animals such as rats
and squirrels may get inside the unit and
cause damage to the unit.
AM0@@FXMDCH_IM_EN_03408A(1).indd 17 2013-03-04 오후 4:28:17