33
ENGLISH
You must install an earth leakage breaker.
- ELCB(Earth Leakage Circuit Breaker)
- MCCB(Molded Case Circuit Breaker)
- ELB(Earth Leakage fuse breaker)
Manufacturers are not responsible for re caused by not installing ELCB or MCCB.
Install the cabinet panel near the outdoor unit for service convenience and emergency operation switch o.
You must install a circuit breaker that can prevent excess current and shut off the electric leakage on the outdoor
unit.
CAUTION
Specification for circuit breaker and power supply cord
Power supply cord is not supplied with air conditioner.
Select the power supply cord in accordance with relevant local and national regulations.
Wire size must comply with the applicable local and national code.
The appliance shall be provided with a certified power supply cord and interconnection cord complying with the national
regulations of the countries in which the appliance is to be sold.
Model Power source RLA
FLA
MCA MOP
FAN1 FAN2
AM036FXMDCH
208~230V~, 60Hz
16.9 0.6 0.6 23 40
AM048FXMDCH 22.1 0.6 0.6 29 50
AM053FXMDCH 26.0 0.6 0.6 34 55
1) RLA is based on AHRI 210/240 colling standard condition [Indoor temp. :
26.C/80°F(DB) / 19.46°C/6F(WB), Outdoor temp. : 3C/95°F(DB)]
2) Voltage tolerance is ± 10%.
3) Maxium allowable voltage between phases is 2%.
Symbols
RLA : Rated Load Ampere
FLA : Full Load Ampere
MCA : Minumum Circuit Ampere (A)
MOP : Maximum Overcurrent Protective Device (A)
NOTE
Tightening power terminal
Connect the cables to the terminal board using the compressed ring terminal.
Use rated cables only.
Connect the cables with driver and wrench that can apply the rated torque to the screws.
Make sure that appropriate tightening torque is applied for cable connection. If the terminal is loose, arc heat may occur
and causere and if the terminal is connected toormly, terminal may get damaged.
Tightening torque
M4 12.0~15.0 kgfcm 1.2~1.5 N•m Communication : F1, F2
M5 20.0~25.0 kgfcm 2.0~2.5 N•m 1 phase AC power : L1, L2