Troubleshooting
4-60 Samsung Electronics
Outdoor unit’s option switch setting error (Using E2P option of other models or emergency
operation for compressor malfunction option setting was enabled on all compressors of
corresponding outdoor unit). (E-560)
Outdoor unit Display E-560
Judgement Method •Referthenextpage.
Cause of problem
•Optionsettingerrorofoutdoorunit.
(E2P option use of other model or set of the relevant outdoor unit, compressor
breakdown)
Is the Compressor
breakdown
setting value is "not set"?
Set the compressor breakdown setting value as
"not set"
When setting breakdown for repair and replace
of compressor : Change the setting after replace.
Yes
No
Is the outdoor unit
EEPROM accurately
connected to
connector?
Connect outdoor unit EEPROM and then reset.
No
Yes
Download relevant model
EEPROM and then reset.
Execute automatic commissioning for UP
cancellation after EEPROM download.