EasyManua.ls Logo

Samsung AM080KXMDFH/TC - Appropriate Measures for Different Symptom

Samsung AM080KXMDFH/TC
128 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Samsung Electronics 4-13
4-2 Appropriate Measures for Different Symptom
Error due to repeated address setting
(when 2 or more devices has same address within the network). (E-108)
Outdoor unit Display E-108
Indoor unit Display
Operation Defrost Timer Fan Filter / EMI
× ×
×
: ON
: Flash ×: OFF
Judgement Method •Referthenextpage.
Cause of problem •IndoorunitandMCUaddressduplication.
After completely tracking the outdoor unit, check
the occurrence of E108.
Has E108 occurred?
Yes
Yes
Check the rotary switch of the address of the
installed MCU to check any duplicate address.
End.
Check the machine where the error
occurred in the outdoor unit display :
- If SEG1 is A, an indoor unit; and
- If SEG1 is C, MCU.
Find a unit whose address is duplicated in the
manual address view on the view mode of the
outdoor unit display. (If there is an address that
does not appear in the manual address view even
though a unit is actually installed, the address is
duplicated.)
Ex.) When the following is displayed in the view
mode at the site where No. 0 to 4 are installed,
possible to judge that the address of no. 3 indoo
r
unit is duplicated. A000 A001 A002 A004
E108 occurring
machine
No
MCU
Replace Inverter PCB.
Replace Inverter PCB.
Check the manual address
view in the view mode.
(Press and hold K4 switch to enter)
K3 reset
When the system is reset through K3 reset, the previous error
(E108) on the display is sometimes indicated. This indicates
the error left previously in the indoor unit during the course
of performing resetting and addressing the whole system
after the outdoor unit is reset. When addressing is completed,
the error indication disappears (up to 5 minutes required).
Whole system power reset
- To solve the problem through the power reset after
the address is reset the power reset of individual units
is meaningless and the power of the whole system
must be reset.

Related product manuals