2-8 Samsung Electronics
Outdoor Unit
Type
Model AM080KXMFGH/ID AM100KXMFGH/ID AM080KXMFHH/MG AM100KXMFHH/MG
Power Supply Φ, #, V, Hz 3,4,380-415,50 3,4,380-415,50 3,4,400,60 3,4,400,60
Mode - HEAT PUMP HEAT PUMP HEAT PUMP HEAT PUMP
Performance
HP HP 8 10 8 10
Capacity
(Nominal)
Cooling
kW 22.4 28.0 22.4 28.0
Btu/h 76,400 95,500 76,400 95,500
Cooling @46°C
kW 19.0 25.0 19.0 25.0
Btu/h 64,800 85,300 64,800 85,300
Heating
kW 25.2 31.5 25.2 31.5
Btu/h 86,000 107,500 86,000 107,500
Power
Power Input
Cooling kW 5.33 6.83 5.33 6.83
Cooling @46°C 5.43 7.60 5.43 7.60
Heating 5.59 7.14 5.59 7.14
Current Input
Cooling A 8.26 10.58 8.26 10.58
Cooling @46°C 8.97 11.83 8.97 11.83
Heating 8.93 11.44 8.93 11.44
MCA A 21.5 23.5 21.5 23.5
MFA (MOP) A 30 30 30 30
COP
Nominal Cooling W/W 4.20 4.10 4.20 4.10
Nominal Cooling @46°C W/W 3.50 3.29 3.50 3.29
Nominal Heating W/W 4.51 4.41 4.51 4.41
Efficiency IPLV W/W Not applicable Not applicable Not applicable Not applicable
Compressor
Type -
Samsung Scroll
Inverter
Samsung Scroll
Inverter
Samsung Scroll
Inverter
Samsung Scroll
Inverter
Output kW × n 5.18 x 1 6.39 x 1 5.18 x 1 6.39 x 1
Model Name - DS-GB052FAVB DS-GB066FAVB DS-GB052FAVB DS-GB066FAVB
Oil
Type - PVE PVE PVE PVE
Comp Charge cc 1100 1100 1100 1100
Line Charge cc 1200 1200 1200 1200
Fan
Type - Propeller Propeller Propeller Propeller
Output × n W 244*2 244*2 244*2 244*2
Air Flow Rate [C/H] CMM 190 / 190 190 / 190 190 / 190 190 / 190
Piping
Connections
Liquid Pipe
Φ, mm 9.52 9.52 9.52 9.52
Φ, inch 3/8" 3/8" 3/8" 3/8"
Gas Pipe
Φ, mm 19.05 22.22 19.05 22.22
Φ, inch 3/4" 7/8" 3/4" 7/8"
Installation Max. Length m 160 160 160 160
Limitation Max. Height m 50 50 50 50
Refrigerant
Type - R410A R410A R410A R410A
Factory Charging kg 3.7 4.3 3.7 4.3
External
Dimension
Net Weight kg 145 155 145 155
Shipping Weight kg 158 168 158 168
Net Dimensions (W×H×D) mm 940x1630x460 940x1630x460 940x1630x460 940x1630x460
Shipping Dimensions (W×H×D) mm 1020x1820x575 1020x1820x575 1020x1820x575 1020x1820x575
Operating Cooling °C -5 ~ 54 -5 ~ 54 -5 ~ 54 -5 ~ 54
Temp. Range Heating °C -25 ~ 24 -25 ~ 24 -25 ~ 24 -25 ~ 24
1) Nominal cooling capacities are based on;
- Indoor temperature : 27°C DB, 19°C WB
- Outdoor temperature : 35°C DB, 24°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
2) Nominal heating capacities are based on;
- Indoor temperature : 20°C DB, 15°C WB
- Outdoor temperature : 7°C DB, 6°C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m