Troubleshooting
4-4 Samsung Electronics
How to display integrated error code
• Meaningsoffirstalphabeticalcharacter/numberoferrorcode.
Error code
• Orderoferrordisplay
Displayed alphabet Explanation
When displaying Error 101~700.
When displaying Error 701~800.
Displays address of subordinate within the set C003 : INV1 PCB / C002 : FAN PCB.
When displaying outdoor unit address.
Ex) U200: Outdoor unit 1, U201: Outdoor unit 2, U202: Outdoor unit 3, U203: Indoor
unit 4.
When displaying indoor unit address.
Ex) A000: Indoor unit address 0, A001: Indoor unit address 1, A002: Indoor unit
address 2.
Classification
Error display sequence Display examples
Display method for error that occurred
in indoor unit
Error Number
Indoor unit address
Error Number, repeat display
E471
A002
E471
A002
Display method for error that occurred
in outdoor unit and other methods of
error display
Error Number
Outdoor unit address
Error Number, repeat display
E471
U200
E471
U200
E206
C001
E206
C002
No. Code Explanation
1 E-108
Error due to repeated address setting(when 2 or more devices has same address within the
network).
2 E-121 Error on indoor temperature sensor of indoor unit(Short or Open).
3 E-122 Error on EVA IN sensor of indoor unit(Short or Open).
4 E-123 Error on EVA OUT sensor of indoor unit(Short or Open).
5 E-128 EVA IN temperature sensor of indoor unit is detached from EVA IN pipe.
6 E-129 EVA OUT temperature sensor of indoor unit is detached from EVA OUT pipe.
7 E-149 Error due to AHU MASTER indoor unit sensor setting.
8 E-151 Error due to opened EEV of indoor unit(2nd detection).
9 E-152 Error due to closed EEV of indoor unit(2nd detection).
10 E-153 Error on oat switch of indoor unit(2nd detection).
11 E-154 RPM feedback error of indoor unit.
12 E-162 EEPROM error of MICOM(Physical problem of parts/circuit).
13 E-163 Indoor units remote controller option input is incorrect or missing, Outdoor unit EEPROM data error.
14 E-198 Error due to disconnected thermal fuse of indoor unit (Temperature increase of the terminal block).
15 E-201
Communication error between indoor and outdoor unit (Installation number setting error repeated
indoor unit address, indoor unit communication cable error).
16 E-202
Communication error between indoor and outdoor unit(Communication error on all indoor unit,
outdoor unit communication cable error).