EasyManua.ls Logo

Samsung AM080KXMDFH/TC - Page 85

Samsung AM080KXMDFH/TC
128 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting
Samsung Electronics 4-43
Compressor operation stop due to discharge temperature protection control. (E-416) (cont.)
Outdoor unit Display E-416
Indoor unit Display
Duct, Cassette (1 / 2Way), Console, Ceiling
Operation Defrost Timer Fan Filter / MPI
× ×
Cassette (4Way / Mini 4Way)
Operation Defrost Timer Filter
×
Duct, Cassette (1/2 Way), Console, Ceiling
Operation Timer Turbo 24°C 27°C
× ×
: ON
: Flash ×: OFF
Judgement Method
•JudgmentMethod:Inspectionwhenthevalueoflowpressuresensoris
1.8kg/cm2,orlessforairconditioningand0.8kg/cm²forheating.
Cause of problem
•Refrigerantshortage
•Electronicexpansionvalveisblocked.
•Servicevalveblocked
•Defectivedischargetemperaturesensor
•TOPtemperaturesensordefective
•Blockedpipeanddefective
•Leakageofcompressordischargecheckvalveofnot-go-endoutdoorunit

Related product manuals