Setting an indoor unit address and installation option
SEG 3, 4, 5, 6, 8, 9 additional information
When the SEG 3 is set as “1” and follow Auto Change Over for HR only operation, it will operate as follows.
A : Set with SEG4(˚C)
B : Set with SEG5(˚C)
C : Set with SEG6(˚C)
D : Set with SEG8(˚C)
Cooling Thermo O
Heating Thermo O
Cooling Thermo On
Heating Thermo On
B
C
D
Ts
A
c
a
Temp.
d
b
Standard temp. for Heating
Standard temp. for Cooling
Standard temp. for Heating
Cooling
Standard temp. for
Cooling Heating
Set temp. for Auto mode
Cooling/Heating mode can be changed when Thermo O status is maintained during the time with SEG9.