32
Option No. : 05XXXX-1XXXXX-2XXXXX-3XXXXX
Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6
Explanation
PAGE MODE
Use of Auto Change
Over for HR only in
Auto mode
(When setting SEG3)
Standard heating temp.
Oset
(When setting SEG3)
Standard cooling temp.
Oset
(When setting SEG3)
Standard for mode
change
Heating
→
Cooling
Remote
Controller
Display
Indication
and Details
Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details
0 5
0
Follow
product
option
0 0°C 0 0°C 0 1°C
1
Use Auto
Change
Over for
HR only
1 0.5°C 1 0.5°C 1 1.5°C
2 1°C 2 1°C 2 2°C
3 1.5°C 3 1.5°C 3 2.5°C
4 2°C 4 2°C 4 3°C
5 2.5°C 5 2.5°C 5 3.5°C
6 3°C 6 3°C 6 4°C
7 3.5°C 7 3.5°C 7 4.5°C
Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
Explanation PAGE
(When setting SEG3)
Standard for mode
changing
Cooling
→
Heating
mode
(When setting SEG3)
Time required for mode
change
Compensation option
for Long pipe or height
diference between
indoor units
Remote
Controller
Display
Indication
and Details
Indication Details Indication Details Indication Details Indication Details
1
0 1°C 0 5 min. 0
Use default
value
1 1.5°C 1 7 min.
1
1) Height
difference
1)
is more than
30m or
2) Distance
2)
is longer
than 110m
2 2°C 2 9 min.
3 2.5°C 3 11 min.
4 3°C 4 13 min.
2
1) Height
difference
1)
is
15~30m or
2) Distance
2)
is 50~110m
5 3.5°C 5 15 min.
6 4°C 6 20 min.
7 4.5°C 7 30 min.
05 series installation option(Detailed)
Setting an indoor unit address and installation option (Continued)
NASA_Big Duct_AM@@@FNHDEH@_IM_EN_03653A-06.indd 32 2016-12-01 오후 3:07:00