10. Capacity Correction10. Capacity Correction
Outdoor units
Cooling
Pipe Length (m)
5 10 12.5 15
Level Difference (m)
8 - 0.96 0.94 0.91
5 0.99 0.97 0.95 0.92
0 1 0.98 0.96 0.93
-5 0.99 0.97 0.95 0.92
-8 - 0.96 0.94 0.91
Heating
Pipe Length (m)
5 10 12.5 15
Level Difference (m)
8 - 0.96 0.94 0.91
5 0.99 0.97 0.95 0.92
0 1 0.98 0.96 0.93
-5 0.99 0.97 0.95 0.92
-8 - 0.96 0.94 0.91