10
Installation Procedure
English
Installation Procedure
Connecting the main power cable
MCCB
Communication cable
Indoor Unit
Outdoor to indoor
power cable
ELB
Cable tie
Electrical
component box
Main power
cable
The appearance of the unit may be different
from the picture depending on the model.
Power supply
1(L)
L
F1
2(N) N
F2
CAUTION
You should connect the power cable into the power cable terminal and fasten it with a clamp.
The unbalanced power must be maintained within 2% of supply rating.
If the power is unbalanced greatly, it may shorten the life of the condenser. If the unbalanced power is exceeded over
4% of supply rating, the indoor unit is protected, stopped and the error mode indicates.
To protect the product from water and possible shock, you should keep the power cable and the connection cord of
the indoor and outdoor units within ducts. (with appropriate IP rating and material selection for your application)
Ensure that main supply connection is made through a switch that disconnects all poles, with contact gap of a least
0.12 inch(3mm).
Devices disconnected from the power supply should be completely disconnected in the condition of overvoltage
category.
Keep distances of 1.97 inch(50mm) or more between power cable and communication cable.
DB68-11579A-00_IM_RAC oudoor_AA_EN_.indd 10DB68-11579A-00_IM_RAC oudoor_AA_EN_.indd 10 2022-01-12 오후 1:37:502022-01-12 오후 1:37:50