2-6
2-3 Product Specifications
MODEL
INDOOR UNIT EH052EAMC EH070EAMC DH094EAMC
OUTDOOR UNIT UH052EAMC UH070EAMC UH094EAM1C
Capacity
Cooling
W 5500 6800 8800
Heating
W 6300 7500 9500
C.O.P
Cooling
W/W 2.82 2.81 2.41
Heating
W/W 3.15 3.1 2.71
Power Supply
Φ/V/Hz
1Φ, 220-240V~,50Hz
Power Input
Cooling W 1950 2420 3650
Heating W 2000 2420 3500
Running
Current
Cooling A 9.0 11.1 16.5
Heating A 9.0 11.1 15.5
Indoor Unit
Fan Speed
Hi r.p.m 1340± 50 1320± 50 1340± 50
Mid r.p.m 1260± 50 1250± 50 1270± 50
Low r.p.m 1075± 50 1080± 50 1080± 50
Air Flow Rate
Hi
m
3
/min
14.9 20.5 24.4
Mid
m
3
/min
13.8 19 22.7
Low
m
3
/min
11.2 16.5 18.4
Noise Level(Cooling/Heating) dB(A) 42/43 45/46 47/48
Heat
Exchanger
Type
ANTIBACTERIA
RowsxStagesxFin pitch 3×12×1.3 2×12×1.3 3×10×1.3
Fan
Type Sirocco
INPUT
W
150 150 200
Dimensions
H mm 199 199 260
W mm 900 1100 1150
D mm 600 600 480
Weight Net/Gross kg 26 31 35
Outdoor Unit
Fan Speed
Hi r.p.m 940± 40 880± 40 980± 50
Low r.p.m 450± 40 450± 40 500± 50
Noise Level(Cooling/Heating) dB(A) 59/60 60/61 63/64
Fan
Type Propeller
INPUT
W
140 150 200
Compressor
Type Rotary
Model G8D190JUAEH G5A240JUAEM NN40VAAMT
Output kW 5860 7063 10200
O.L.P Type Internal
Heat
Exchanger
Charge g 1500 1700 1800
Control EEV EEV EEV
Type Louver
RowsxStagesxFin pitch 2×28×1.4 2×28×1.4 2×36×1.5
Dimensions
H mm 648 648 798
D mm 310 310 310
W mm 880 880 880
Weight Net/Gross kg 59 60 74