SPECIFICATION OF CONTROL MODULE
4
High Load Prevention Control(During Heating)
4-2. High Load Prevention Control (During Heating)
4-2-1. Operation Pattern
4-2-2. Operation specification
Œ
Prevention control of high temperature according to the outdoor temperature
– Outdoor temperature 14˚C : Outdoor FAN LOW
– Outdoor temperature 12˚C : Outdoor FAN HIGH
´
Prevention control of high temperature according to the indoor heat exchanger temperature
– Outdoor fan / COMPor is controlled by detecting the indoor heat exchanger during control of outdoor fan according to the outdoor
temperature.
– Indoor heat exchanger temperature 60(58)˚C : Outdoor FAN OFF(high temperature prevention 1st)
(( )temperature is for model 23Z)
– Indoor heat exchanger temperature 65˚C for 20 seconds : Outdoor FAN OFF, compressor OFF
(high temperature prevention 2nd)
– Release of the high temperature control based on the indoor heat exchanger
! The 1st release of high temperature prevention
! Release at outdoor temperature 14˚C: indoor heat exchanger temperature 55(52)˚C(( ) temperature is for model 23Z)
! Release at outdoor temperature 12˚C: Indoor heat exchanger temperature 52˚C
@ The 2nd release of high temperature prevention
! Release at indoor heat exchanger temperature 52˚C
ˇ
Indoor fan control at the control of high temperature prevention
– Indoor fan control during 1st high temperature prevention
breeze is set at wind volume weak, weak weak, strong strong
In model 23Z, strong wind at outdoor temperature 14˚C, the temperature of indoor heat exchanger 55˚C
– Indoor fan control at the 2nd high temperature prevention : breeze