● ACH3600G, ACH4400G, CH36ZA, CH44ZA, CH36CA, CH44CA
Indoor Unit Outdoor Unit
*Allowable pipe length : Max. 30m
*Allowable drop distance : Max. 15m
*Amount of refilling per extension length of 1m;
When extending the pipe length by more than 5m, 50gr(35gr: Outdoor Unit is higher than Indoor Unit) of R-22
refrigerant should be refilled per extension length of 1m. : ACH4400G, CH44ZA
When extending the pipe length by more than 5m, 60gr(45gr: Outdoor Unit is higher than Indoor Unit) of R-22
refrigerant should be refilled per extension length of 1m. : ACH3600G, CH36ZA
When extending the pipe length by more than 5m, 40gr(40gr: Outdoor Unit is higher than Indoor Unit) of R407C
refrigerant should be refilled per extension length of 1m. : CH44CA
When extending the pipe length by more than 5m, 45gr(40gr: Outdoor Unit is higher than Indoor Unit) of R407C
refrigerant should be refilled per extension length of 1m. : CH36CA
Refrigerating Cycle Block Diagram (Cont.)