23
Essential
3. Electric Characteristics
Capacity
Model
Power Supply Voltage Range
Running Current [A] Current [A] ODU Fan Motor
Hz Voltage
Min.
(-10%)
Max.
(+10%)
HP kW
Cooling Heating MCA MFA kW FLA [A]
10 28.0 AM100MXVDGH/ET 50 380-415 342 456 11.5 12 21.1 32 0.83 2.4
12 33.6 AM120MXVDGH/ET 50 380-415 342 456 15 14.8 25 32 0.83 2.4
14 40.0 AM140MXVDGH/ET 50 380-415 342 456 19.9 17.9 25 32 1.24 3.8
16 45.0 AM160MXVDGH/ET 50 380-415 342 456 22.1 20.3 32 40 1.24 3.8
18 50.4 AM180MXVDGH/ET 50 380-415 342 456 25.7 23.7 39.2 50 1.24 3.8
20 56.0 AM200MXVDGH/ET 50 380-415 342 456 23 24 42.2 63 1.66 4.8
22 61.6 AM220MXVDGH/ET 50 380-415 342 456 26.5 26.8 46.1 63 1.66 4.8
24 6 7. 2 AM240MXVDGH/ET 50 380-415 342 456 30 29.6 50 63 1.66 4.8
26 73.6 AM260MXVDGH/ET 50 380-415 342 456 34.9 32.7 50 63 2.07 6.2
28 80.0 AM280MXVDGH/ET 50 380-415 342 456 39.8 35.8 50 63 2.48 7.6
30 84.0 AM300MXVDGH/ET 50 380-415 342 456 40.7 38.5 64.2 75 2.07 6.2
32 90.4 AM320MXVDGH/ET 50 380-415 342 456 45.6 41.6 64.2 75 2.48 7. 6
34 95.4 AM340MXVDGH/ET 50 380-415 342 456 47.8 44 71.2 80 2.48 7. 6
36 100.8 AM360MXVDGH/ET 50 380-415 342 456 51.4 47.4 78.4 90 2.48 7. 6
38 107.2 AM380MXVDGH/ET 50 380-415 342 456 49.9 4 7. 5 75 90 2.9 8.6
40 113.6 AM400MXVDGH/ET 50 380-415 342 456 54.8 50.6 75 90 3.31 10
NOTE
MCA : Minimum circuit amperes
MFA : Maximum fuse amperes
FLA : Full load amperes

Table of Contents