1. Combination Table
Outdoor Units
Essential
System Model Capacity of Single Unit (HP)
Capa Code No. of Modules 8HP 10HP 12HP 14HP 16HP 18HP 20HP 22HP 24HP 26HP 28HP 30HP
10HP AM100MXVDGH/ET 1 1
12HP AM120MXVDGH/ET 1 1
14HP AM140MXVDGH/ET 1 1
16HP AM160MXVDGH/ET 1 1
18HP AM180MXVDGH/ET 1 1
20HP AM200MXVDGH/ET 2 2
22HP AM220MXVDGH/ET 2 1 1
24HP AM240MXVDGH/ET 2 2
26HP AM260MXVDGH/ET 2 1 1
28HP AM280MXVDGH/ET 2 2
30HP AM300MXVDGH/ET 2 1 1
32HP AM320MXVDGH/ET 2 1 1
34HP AM340MXVDGH/ET 2 1 1
36HP AM360MXVDGH/ET 2 2
38HP AM380MXVDGH/ET 3 2 1
40HP AM400MXVDGH/ET 3 1 2
NOTE
Ma
ke sure to use an indoor unit that is compatible with DVM S.
Indoor units can be connected within the range indicated in following table.
If the total capacity of the connected indoor units exceeds the indicated maximum capacity, cooling and heating
capacity of the indoor unit may decrease.
Total capacit
y of the connected indoor units can be allowed from 50% to 130% of the total outdoor unit capacity.

You can connect maximum 64 indoor units to the outdoor unit. Maximum quantity of connectable indoor unit is set to 64
since outdoor unit only support up to 64 communication address. Indoor unit address can be
assigned from 0~63. If the indoor unit address was assigned from 64~79, E201 error will occur.

In case of combining modules more than 90HP, please consult the manufacturer when connecting the indoor unit and
deciding on piping length in accordance with design of the building.