39
ENGLISH
Additional refrigerant
H/P H/R
Ø12.70 (5 m)
Ø12.70 (5 m)
Ø12.70 (5 m)
Ø6.35 (5 m)
Ø6.35 (10 m)
Ø6.35 (15 m)
Ø9.52 (10 m)
Ø9.52 (10 m)
Ø9.52 (10 m)
Ø9.52 (10 m)
Ø6.35 (5 m)
Ø9.52 (10 m)
46.4kW
4.5kW
5.6kW
5.6kW
7.1kW
7.1kW
7.1kW
7.1kW
3.6kW
Ø9.52 (1 m)
Ø12.70 (5 m)
Ø15.88 (10 m)
Ø12.70 (10 m)
Ø9.52 (15 m)
Ø9.52 (10 m)
Ø12.70 (10 m)
Ø9.52 (18 m)
Ø9.52 (18 m)
Ø9.52
(25 m)
Ø9.52
(15 m)
Ø9.52
(10 m)
MCU
MCU
Ø6.35 (2 m)
2.8kW
7.1kW
11.2kW
7.1kW
11.2kW
7.1kW
7.1kW
7.1kW
Ø6.35 (15 m)
61.6 kW (33.6 kW + 28.0 kW)
Refrigerant pipe installation
f Basic amount of refrigerant within the outdoor unit (kg)
- Amount of additional refrigerant has to be calculated based on the sum of all liquid pipe length.
Classication AM080FXVAG✴ AM100FXVAG✴ AM120FXVAG✴ AM140FXVAG✴ AM160FXVAG✴
Basic type 5.5 5.2 5.5 7.7 7.4
Classication AM180FXVAG✴ AM200FXVAG✴ AM220FXVAG✴
AM240HXVAG✴ AM260HXVAG✴
Basic type 8.7 8.4 8.4 14.3 14.3
Classication AM240MXVGNR AM260MXVGNR AM280MXVGNR
AM300MXVANR
Basic type 14.0 14.0 14.0 14.0
f Amount of additional refrigerant depending on the pipe size (ⓐ)
- Amount of additional refrigerant has to be calculated based on the sum of all liquid pipe length.
Size of liquid pipe Ø 6.35 Ø 9.52 Ø 12.70 Ø 15.88 Ø 19.05 Ø 22.22 Ø 25.40 Ø 28.58
Additional amount (kg/m) 0.02 0.06 0.125 0.18 0.27 0.35 0.53 0.65
- For the indoor unit already connected to EEV kit, the additional refrigerant charging is 0.01kg per meter regardless of
the pipe size.