2-4 Samsung Electronics
Product Specifications(cont.)
QAN100JSKLKN
Power Source 220 - 240 V~, 50 / 60 Hz
Ventilation Mode Heat-Ex Ventilation By-Pass Ventilation
The Level of the Air Volume Turbo High Low Turbo High Low
Power Supply(W) 450 280 155 450 280 155
Air Volume(m³/h) 1000 1000 690 1000 1000 690
External Static Pressure(Pa) 155 90 75 155 90 75
Temperature Exchange
Efficiency(%)
Cooling 70 70 74 - - -
Heating 70 70 74 - - -
Enthalpy Exchange
Efficiency(%)
Cooling 50 50 55 - - -
Heating 70 70 76 - - -
Size(widthxheightxdepth)(mm) 1220 × 340 × 1135
Weight(kg) 67
Duct Size(mm) 250
Trial Operation Conditions
1. Air Volume/ External Static Pressure, Comply with KS Heat Exhaust Ventilation System Standards(KS B6879).
2. Heat Exchange/Temperature Exchange Efficiency, Comply with regulations to pro-
mote high efficiency energy devices,
[Cooling], Indoor(24˚C DB/17˚C WB), Outdoor(35˚C DB/24˚C WB)
[Heating], Indoor(22˚C DB/13.9˚C WB), Outdoor(2˚C DB/0.44˚C WB)