8-8 Samsung Electronics
1) * The total option codes are 24 digits. You can set six digits at a time and it is distinguished by page number.
Press the Timer button to go to the next page.
t Options can be set from SEG1 to SEG24
SEG1, SEG7, SEG13, and SEG19 are page option so they cannot be set nor be displayed
SEG2 is the option type which cannot be set
When SEG2~SEG6 and SEG8~SEG12 are set, "On" is displayed and when SEG14~18 and
.
SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
0XXXXX1XXXXX
SEG13SEG14SEG15 SEG16 SEG17 SEG18 SEG19 SEG20 SEG21 SEG22 SEG23SEG24
2XXXXX3 XXXXX
On (SEG2~SEG6, SEG8~SEG12) Off (SEG14~18, SEG20~24)
t .
SEG2~SEG6, SEG8~SEG12
On(Heat-EX By Pass Auto Quiet Away)
SEG14~SEG18, SEG20~24
By Pass Auto Quiet Away)
p
<SEG 2, 3>
PAGE 1
PAGE 6
PAGE 2
PAGE 7
PAGE 3
PAGE 8
PAGE 4
PAGE 9
PAGE 5
PAGE 10
<SEG 14, 15>
<SEG 4, 5>
<SEG 16, 17>
<SEG 6, 8>
<SEG 18, 20>
<SEG 9, 10>
<SEG 21, 22>
<SEG 11, 12>
<SEG 23, 24>
p
p
p
p
p
pp
p
Caution
2) * When setting the address or option, you can set the target device with sub menu no.1.
3) * Power Master Reset is a setting needed to supply optimized power to ERV wired remote controller when multiple indoor units or
ERVs are connected to ERV wired remote controller in a group.
4) * RMC(1) : 0~F / RMC(2) : 0~F (hexadecimal)
When RMC(1) is F, RMC(2) can be set up to E. (RMC(1) : Group channel, RMC(2) : Group address)
5) * Displaying address of ERVs (hexadecimal display) e.g. 30 00 0B
6) * Fan step setting is available only when one ERV is connected.
Using installation/service mode of ERV wired remote controller(cont.)