17
Outdoor units
*1) Mode
HP : Heat Pump, HR : Heat Recovery
*2) Norminal cooling capacities are based on;
Indoor temperature : 26.7°C DB, 19.4°C WB(80°F DB, 67°F WB)
Outdoor temperature : 35°C DB, 23.9°C WB(90°F DB, 75°F WB), Equivalent refrigerant piping : 7.6m(25ft) , Level differences : 0m(0ft)
*3) Norminal heating capacities are based on;
Indoor temperature : 21.1°C DB, 15.6°C WB(70°F DB, 60°F WB)
Outdoor temperature : 8.3°C DB, 6.1°C WB(47°F DB, 43°F WB), Equivalent refrigerant piping : 7.6m(25ft) , Level differences : 0m(0ft)
*4) Sound level was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.
*5) Specifications are subject to change without prior notice for product improvement.
Type
Model Name
RVXVHT250FE RVXVHT275FE
Model Basic
RVXVHT075FE
1
RVXVHT100FE
2
RVXVHT125FE
2
Power Supply Ø/ V/ Hz
3/ 208~230/ 60 3/ 208~230/ 60
Mode
1)
-
Heat Pump Heat Pump
Performance
US Ton TON
20 22
Horse Power HP
25.0 27.5
Nominal
Capacity
Cooling
2)
Btu/h
240,000 264,000
US RT
20.0 22.0
Heating
3)
Btu/h
270,000 297,000
US RT
22.5 24.8
Power
Nominal Input
Cooling
kW
21.4 20.5
Heating
20.2 19.3
Nominal Running
Current
Cooling
A
73.6 76.6
Heating
66.0 72.4
Circuit Breaker (MCCB/ELB/ELCB) A
60 + 60
50 + 50 + 50
COP
Cooling -
3.29 3.77
Cooling (US Only) Btu/Wh
11.21 12.88
Heating -
3.92 4.51
Compressor
Model
ZPJ72* ZPJ83* ZPI61* ZPI83* ZPJ72* ZPJ83* ZPI61* ZPI83*
Type -
DVI Scroll FVI Scroll DVI Scroll FVI Scroll
Number EA
2 2 3 3
Piston Displacement
cc/Rev
77.2 77.2 67.1 58.1
in³/Rev
4.711 4.711 4.095 3.545
Output kW
7.91 7.91 6.94 5.83
Lubricant
Type -
3MAF POE 3MAF POE
Charging
cc
1,685 1,685 1,685 1,685
fl. oz.
57 57 57 57
Fan
Type / Control -
Propeller/BLDC Propeller/BLDC
Motor Output W
(630) x 2 (630) x 3
Airflow Rate
m
3
/min
(180) x 2 (170) x 3
CFM
(6357) x 2 (6004) x 3
External Static
Pressure
Max.
Pa
78.5 78.5
WG
0.315 0.315
Safety
Devices
Mechanical Type
-
High Pressure Switch High Pressure Switch
-
Comp./Accum. Crank Case Heater Comp./Accum. Crank Case Heater
-
Fuse for PCB Fuse for PCB
Electronic Type
-
Over-voltage Protection Over-voltage Protection
-
Current Transformer Current Transformer
-
Fan motor Voltage Protection Fan motor Voltage Protection
Piping
Connections
Liquid
Ø, mm
19.05 19.05
Ø, inch
3/4 3/4
Gas
Ø, mm
34.93 34.93
Ø, inch
1 3/8 1 3/8
Oil (Flare)
Ø, mm
6.35 6.35
Ø, inch
1/4 1/4
Installation
Limitation
Max. Length
m
200 200
ft
656 656
Max. Height
m
50 (40) 50 (40)
ft
164 (131) 164 (131)
Refrigerant
Type -
R410A R410A
Factory Charging
kg
(9) x 2 (6.5) x 1 + (7.5) x 2
lbs
(19.84) x 2 (14.33) x 1 + (16.53) x 2
Sound
4)
Sound Pressure dB(A)
62 63
Set Size
Net Weight
kg
(280) x 2 (240) x 3
lbs
(617) x 2 (529) x 3
Shipping Weight
kg
(297) x 2 (253) x 3
lbs
(655) x 2 (558) x 3
Net Dimensions (WxHxD)
mm
(1200 x 1668 x 765) x 2 (880 x 1668 x 765) x 3
inch
(47 1/4 x 65 5/8 x 30 1/8) x 2 (34 5/8 x 65 5/8 x 30 1/8) x 3
Shipping Dimensions (WxHxD)
mm
(1268 x 1888 x 832) x 2 (948 x 1888 x 832) x 3
inch
(49 7/8 x 74 3/8 x 32 3/4) x 2 (37 3/8 x 74 3/8 x 32 3/4) x 3
Cable
Main Power (Below 50m) AWG #
Separate electrical connection for each outdoor units Separate electrical connection for each outdoor units
Communication AWG #
AWG 16~18 AWG 16~18
Operating
Temp. Range
Cooling
°C
-5~46.1 -5~46.1
°F
23~115 23~115
Heating
°C
-20~24 -20~24
°F
-4~75 -4~75