EasyManua.ls Logo

Samsung SH09AS2 - Page 82

Samsung SH09AS2
94 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SAMSUNG | 81
TROUBLESHOOTING
8
1. Check the assembly condition of the sensor connector(CN43) on the indoor unit Main PCB and if not assembled, reassemble the
connector accurately.
2. Detach the room pipe sensor connector(CN43) and check the resistance between connector 3 and 4.
If the above data is not met, replace the room pipe sensor.
3. Assemble the room pipe sensor to PCB, plug in, and check the voltage of connector 3 and 4. If the resistance is below 0.5V or
over 4.9V, replace the indoor Main PCB. (short or disconnected in the PCB board)
Temperature(˚C)
15
20
25
Temperature(˚C)
30
35
40
Resistance Value(Kohm)
8.31
6.94
5.83
Resistance Value(Kohm)
14.68
12.09
10
Others
The data tolerance
is ±3%.
Room Pipe sensor failure
Indoor unit heat exchanger temperature sensor error
(open or short)
Description
LAMP
OPERATION TIMER TURBO
7-segment
Display
: Lamp flickering
: Lamp off
Troubleshooting for Non Inverter (cont.)
DB98_16444A(1)_2 2/9/04 10:05 AM Page 81

Other manuals for Samsung SH09AS2

Related product manuals