SAMWON ENG SU-103SR / SU-105DA Controller User Manual Page 2/4
If you press set for 3 seconds, the value will be saved.
After that the changed value will be applied.
Setting temp value will be in the range of 50~40.
Main Output setting can be changed. Please change the below items appropriately.
(When you press set once, it will move to the next item)
* DIF
&
TYP
Input Value example
TYP = C(Cooler(Converse))
example) Set Temp. 10.0, DIF = 2.0
Relay ON : 12.1, Relay OFF : 10.0
TYP = H(Heater(forward))
example) set temp 10.0, DIF = 2.0
relay ON : 7.9, relay OFF : 10
* dLt
=10, relay on after 10 seconds
* tyP = C
(cooler), use for decreasing the temp.
* tyP = H
(heater), use for increasing the temp.
Auxiliary Output (OUT2) is set as alarm output.
Aauxiliary output is supposed to select one among alarm
output(AL) / periodic timer output 1(t1)/ periodic timer output 2(t2).
Accordingly, factory default should be set as the alarm output.
(The factory default is set as AL, alarm output)
To change the factory default, press up button & set button at the
same time for longer than 3 seconds at the current temperature status.
Until FIL is displayed, keep up button & set button pressed.
When FIL is displayed, please release the above two buttons.
If you press set button several times, you can move to ot2.
When ot2 is displayed, change the setting as below by
pressing (up) & (dn) buttons.
factory
default
Item
Setting Value
Description
ot2
AL
Auxiliary Output is used for Alarm output
7 Installer setting
Installer setting item (OUT1)
On/Off rated control
At the current temp, press
set for 3 seconds
Forward/converse
C:Cooler & H:Heater
ON delay timer
0sec~300sec
Output OFF~
ON range
0.1~25.0
Sensor Input
Compeansation
-30~+30
Set press
return to Main
Set press for 3sec, Data saved
Return to the current temp.
Alarm Output
Auxiliary Output setting temp:
Separate target setting
possible from OUT1
Timer Output
Only for SU-105DA Installer setting Item (OUT2)
Output of SV2
OFF~Output ON
Range (0.1~25.0)
Auxiliary delay Timer
(0~300sec)
Auxiliary Forward/converse
C:Cooler & H:Heater
Manual Defrost Time:
1~999Min
refer to 11 refrigerator
setting.
ON time(Defrost operating
time): 0~999Min
*Attention: 0 - indefinite
OFF status
OFF time(Defrost Stop time):
0~999Min
*Attention: 0 - indefinite
ON status
9. Alarm Output Setting (Auxiliary Output)
At the current temp. press up & set
together for 3 seconds
Until FIL displayed, keep up & set
pressed. When FIL appear, release the
buttons.
if dIF displayed, repeat it again
Set press for 3 seconds, all data saved
and return to the current temp.
Set press
return to Main screen
Measurement value filter(0~9):in strong noise, displayed
value is fluctuated, which will be reduced by averaging the
input value during a certain time. It needs some time for
averaging so that response is late (basic Value : 0)
Factory Setting Item
Setting range upper limit : setting temp is limited
below the assigned value.
Setting range lower limit: setting temp is limited
above the assigned value.
Lock function except setting temp change.
ON:lock / OFF :lock cancelled
When Lock cancelled, it should be OFF and saved.
Select whether or not for decimal unit display
related to temp
0 : No decimal display, related to temp
1 : decimal display, related to temp
It is not displayed if you select
AL at OT2.
Only Items for SU-105DA
OUT2 AL(Alarm) / t1(periodic timer 1) / t2(peiodic
Timer 2) control selection
refer to 9,10 item
When OUT2 timer ON, select display value(refer to
refrigerator setting)
PV : OUT2 timer ON- display current temp value
TIM : OUT2 Timer ON-Remaining time of ONTime(TIME
Lamp flashing) refer to 11
OUT2 Timer ON- OUT2 Timer OFF Temp. setting
(refer to refrigerator setting)
OFF : Not used of OUT2 OFF function on the current
Temp.
-20~30 : Over the setting Temp- OUT2 Timer OFF
Select individual operation of OUT1& OUT2 (refer to
refrigerator setting)
NO : OUT1, OUT2 individual opeation
YES : when OUT2 timer ON, OUT1 OFF
refer to 11