SAMWON ENG SU-103SR / SU-105DA Controller User Manual Page 2/4
▶ If you press set for 3 seconds, the value will be saved.
After that the changed value will be applied.
※ Setting temp value will be in the range of 50~40℃.
▶
Main Output setting can be changed. Please change the below items appropriately.
(When you press set once, it will move to the next item)
* DIF
&
TYP
Input Value example
① TYP = C(Cooler(Converse))
example) Set Temp. 10.0℃, DIF = 2.0
Relay ON : 12.1℃, Relay OFF : 10.0℃
② TYP = H(Heater(forward))
example) set temp 10.0℃, DIF = 2.0
relay ON : 7.9℃, relay OFF : 10℃
* dLt
=10, relay on after 10 seconds
* tyP = C
(cooler), use for decreasing the temp.
* tyP = H
(heater), use for increasing the temp.
① Auxiliary Output (OUT2) is set as alarm output.
▶ Aauxiliary output is supposed to select one among alarm
output(AL) / periodic timer output 1(t1)/ periodic timer output 2(t2).
Accordingly, factory default should be set as the alarm output.
(The factory default is set as AL, alarm output)
▶ To change the factory default, press up button & set button at the
same time for longer than 3 seconds at the current temperature status.
▶ Until FIL is displayed, keep up button & set button pressed.
When FIL is displayed, please release the above two buttons.
▶ If you press set button several times, you can move to ot2.
▶ When ot2 is displayed, change the setting as below by
pressing (up) & (dn) buttons.
Auxiliary Output is used for Alarm output
Installer setting item (OUT1)
At the current temp, press
set for 3 seconds
Forward/converse
C:Cooler & H:Heater
ON delay timer
0sec~300sec
Output OFF~
ON range
0.1~25.0℃
Sensor Input
Compeansation
-30~+30
Set press
–
return to Main
Set press for 3sec, Data saved
Return to the current temp.
Auxiliary Output setting temp:
Separate target setting
possible from OUT1
Only for SU-105DA Installer setting Item (OUT2)
Output of SV2
OFF~Output ON
Range (0.1~25.0)
Auxiliary delay Timer
(0~300sec)
Auxiliary Forward/converse
C:Cooler & H:Heater
Manual Defrost Time:
1~999Min
※ refer to 11 refrigerator
setting.
ON time(Defrost operating
time): 0~999Min
*Attention: 0 - indefinite
OFF status
OFF time(Defrost Stop time):
0~999Min
*Attention: 0 - indefinite
ON status
9. Alarm Output Setting (Auxiliary Output)
At the current temp. press up & set
together for 3 seconds
Until FIL displayed, keep up & set
pressed. When FIL appear, release the
buttons.
※ if dIF displayed, repeat it again
Set press for 3 seconds, all data saved
and return to the current temp.
Set press
–
return to Main screen
Measurement value filter(0~9):in strong noise, displayed
value is fluctuated, which will be reduced by averaging the
input value during a certain time. It needs some time for
averaging so that response is late (basic Value : 0)
Setting range upper limit : setting temp is limited
below the assigned value.
Setting range lower limit: setting temp is limited
above the assigned value.
Lock function except setting temp change.
ON:lock / OFF :lock cancelled
When Lock cancelled, it should be OFF and saved.
Select whether or not for decimal unit display
related to temp
0 : No decimal display, related to temp
1 : decimal display, related to temp
It is not displayed if you select
AL at OT2.
OUT2 AL(Alarm) / t1(periodic timer 1) / t2(peiodic
Timer 2) control selection
※ refer to 9,10 item
When OUT2 timer ON, select display value(refer to
refrigerator setting)
PV : OUT2 timer ON- display current temp value
TIM : OUT2 Timer ON-Remaining time of ONTime(TIME
Lamp flashing) ※ refer to 11
OUT2 Timer ON- OUT2 Timer OFF Temp. setting
(refer to refrigerator setting)
OFF : Not used of OUT2 OFF function on the current
Temp.
-20~30 : Over the setting Temp- OUT2 Timer OFF
Select individual operation of OUT1& OUT2 (refer to
refrigerator setting)
NO : OUT1, OUT2 individual opeation
YES : when OUT2 timer ON, OUT1 OFF
※refer to 11