SAMWON ENG SU-103SR / SU-105DA Controller User Manual Page 3/4
If you press set buttons for 3 seconds, the data will be saved.
Alarm output temperature setting method
In order to set the alarm output temperature, press set button for 3
seconds at the status that the current temperature displayed. If DiF is
displayed, release set button.
if you press set button several times, you can move to SV2.
By pressing up & dn, set buttons, you can change the setting as below.
Installer
Setting
Item
Setting Value
Description
SV2
-40.0~99.9
Setting Alarm Output Temperature
dF2
0.1~25.0
Setting the range from Alarm Output OFF ~
Output ON
dt2
0~300 sec
Setting Alarm output ON delay time value
ty2
H / C
Setting Alarm output heating (H/forward),
cooling (C/converse) value
if you press set button for 3 seconds, the data will be saved.
Example1)Set alarm output temperature at 20.0, dF2 = 5.0, dt2 = 10, ty2 = H
Relay ON : ON after 10 seconds stand-by at 14.9
Relay OFF : 20.0
Example2)Set alarm output temperature at 20.0, dF2 = 2.0, dt2 = 20, ty2 = C
Relay ON : ON after 20 seconds stand-by at 22.1
Relay OFF : 20.0
Alarm Output is working, completely separated from
thermometer operation
1) Setting Method
Auxiliary output is set as periodic timer output.
Auxiliary output is supposed to select one among alarm
output (AL) / periodic timer output 1(t1)/ periodic timer output 2(t2).
Accordingly, factory default should be set as periodic timer output.
(The factory default is set as t1(timer1).
To change the factory default, press up button and set button at the
same time for 3 seconds at the status of the current temperature
displayed.
Until FIL is displayed, keep up button and set button pressed.
When FIL is displayed, release these buttons.
If you press set buttons several times, you can move to ot2.
When ot2 is displayed, change the setting as below by
pressing up & dn buttons.
Factory
default
Item
Setting Value
description
ot2
t1
Auxiliary output is used for periodic timer output1
Refer to NO10 item and 2)periodic timer operation
t2
Auxiliary output is used for periodic timer output 2
refer to NO.10 and 2)Periodic timer operation
If you press set button for 3 seconds, the data will be saved.
Periodic timer output On/Off Time Setting Method.
To set On/Off time, press set button for 3 seconds at the status of
current temperature displayed. When DiF is displayed, release set key.
If you press set button several times, you can move to on.
Change the setting as below by pressing up & dn and set).
Installer
setting
item
Setting value
description
on
0 ~ 999min
Select output ON time value
* Set as 0, continuously OFF without ON
time
oFF
0 ~ 999min
Select Output OFF time value
* Set as 0, Continuously ON without OFF
time.
If you press Set button for 3 seconds, the data are saved.
2) Periodic Timer Operation
Auxiliary Output is set as periodic output
t1.
Timer output (OUT2) is OFF during OFF setting time, Timer Output(OUT2) is
ON during ON setting time. It will be repeated.
Auxiliary Output is set as periodic timer output
t2
During OFF setting time, make the sum of OUT1 ON time (except OUT1
OFF time). And, at the OFF setting time, timer output (OUT2) is made
during ON setting time.
1) Control Setting
OUT1 ouput is connected to COMP control output of refrigerator.
OUT2 output is connected to defrost heater control output.
2) Regulator Setting
(1) COMP(OUT1)
Setting appropriately DIF and DLT of Installers setting items
Select TYP of installers setting items as C(Cooler).
Set the refrigerators operation temperature as the Main Output Setting Value.
(2)Defrost(OUT2)
Select Factory default OT2 item as periodic timer.
Set ON time (defrost time value) of installer setting items
Set normal operation time (defrost OFF time) at OFF time item of installers
setting item.
Set factory default INT as YES, in the case of stopping COMP(OUT1)
operation during defrost time value operation.
In the case of displaying the current temperature of refrigerator during
Defrost function operation, set factory default DP2 item as PV.
In the case of displaying the remaining time, set DP2 as TIM.
10. Periodic Timer Setting (Auxiliary output)
15min Off
5min On
15min Off
5min On
ot2 = t1
on = 5
oFF = 15
Setting
Periodic
Timer Output
40min Off
30min On
40MIN Off
30min On
ot2 = t1
on = 30
oFF = 40
Setting
Periodic
Timer Output
11. Refrigerator Setting
5min On
5min On
ot2 = t2
on = 5
oFF = 150
periodic
timer output
OUT1 ou
tput
ON
OFF
50min
60min
IN
40min
40min
90min
20min
10min On
10min On
ot2 = t2
on = 10
oFF = 250
periodic
timer output
OUT1 output
ON
OFF
100min
50min
100min
70min
80min
100min
50+60+40=150min
40+90+20=150min
Only sum of OUT1(COMP) operation time(except COMP stop time).
When the sum is timer OFF Setting time of 150min,defrost operation 5min.
100+50+100=250M
70+80+100=250M
Only sum of OUT1(COMP) operation time(except COMP top time).
When the sum is timer OFF setting time of 250min,defrost operation10min.