Control Status Message
This can indicate:
OKAY—The control is operating correctly.
Settings Mismatch—The Validate/Apply command failed.
Problem Present—An error has been detected that is not a Warning or Alarm condition.
Switch 1/2 Auto Operation Status
SCADA commands can enable/disable the Automatic Operation mode for each switch.
This indicates a Disabled state for both switches when the Automatic Operation
mode has been disabled on the Operation screen or the faceplate. When the Automatic
Operation mode has been enabled on the Operation screen or the faceplate, this
indicates the state of the Automatic Operation mode congured for each switch by
SCADA. This will have the same indication for both switches if a SCADA command has
not been received.
Switch 1/2 Feature Selected
The Automatic Operation setting is congured on the Setup>General>Automatic Op.
screen. This indicates the setting congured for each switch. Possibilities are:
Sectionalizing Only
• Three-Phase Voltage Loss
• Phase-Loss Protection
• Phase-Loss Protection with Automatic Reclose
Switch 1/2 Identification (only for Dual Overhead Switch Control)
These are read-only elds congured on the Setup>General>SG6800 screen.
Pad-Mount Configuration
This shows the settings for pad-mount conguration only; set on the Setup>General>
Sensor Cong screen.
Active User-Defined Inputs
The three wired inputs at connector J20 on the PS/IO board are congured on the
Setup>Point Mapping>Status>User Dened Inputs screen. This eld displays the
congured User Dened Input Label setpoint when that user-dened digital input is
active.
IntelliLink
®
Setup Software
S&C Instruction Sheet 1045-530 15