Switch Control Setup
Device Serial Number
The serial number is automatically read from the control.
Cabinet Heater On 100% Below This Temperature
If there is a heater in the switch control enclosure and the control is powered by an
external ac source, the heater stays on continuously while the interior enclosure
temperature is below this value. This setpoint is usually set at the factory-default value.
(Minimum value: -50; maximum value: 204; Increment: 1 degree Fahrenheit; Default: 25)
The cabinet temperature is evaluated once every 10 minutes. The temperature at the
thermistor location (on the Power Supply/Control I/O module) is typically 10-15 degrees
Fahrenheit above the ambient air temperature.
Cabinet Heater On 50% Below This Temperature
If there is a heater in the switch control enclosure, and the control is powered by an
external ac source, the heater stays on 50% of the time whenever the interior cabinet
temperature is below this value but above the “Cabinet Heater on 100% Below This
Temperature” value. This setpoint is usually set at the factory-default value. (Minimum
value: -49; maximum value: 205; Increment: 1 degree Fahrenheit; Default: 35)
Switch 1/2 Identification (only for the Dual-Overhead Switch Control)
Enter a custom identier for each switch. This will display on the Operation screen.
Switch 1/2 Serial Number (only for the Dual-Overhead Switch Control)
Enter the serial number for each switch.
S&C Instruction Sheet 1045-530 21