EasyManua.ls Logo

Sanyo C4272R S/C - Page 15

Sanyo C4272R S/C
111 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
15
CAUTION
CAUTION
WARNING
1. This unit requires no additional refrig-
erant charge up to 100 ft. tubing length.
In case of more than 100 ft., additional
refrigerant charge is required. Refer to
Table 1-11.
2. In case of multi type installation,
indoor units should be installed within
the same room. If multi type indoor
units are installed in different rooms,
temperature control may develop prob-
lems because thermostat operation
must follow the thermostat condition of
1 indoor unit only (the main unit).
Always check the gas density
for the room in which the unit is
installed.
Pay special attention to any
location, such as a basement
or recessed area, etc. where
leaked refrigerant can collect,
since refrigerant gas is heav-
ier than air.
22
486
972
1,449
1,935
2,421
2,907
3,384
3,870
4,356
4,842
54
108
161
215
269
323
376
430
484
538
ft.
3
ft.
2
Total amount of refrigerant
Min. indoor floor area
(when the ceiling is 9 ft. high)
Min. indoor volume
44 66 88 lbs.
Range below the
density limit of
0.3 oz./ft.
3
(Countermeasures
not needed)
Range above the
density limit of
0.3 oz./ft.
3
(Countermeasures
needed)
Check of limit density
When installing an air conditioner in a room, it is neces-
sary to ensure that even if the refrigerant gas acciden-
tally escapes, its density does not exceed the limit level.
If the density might exceed the limit level, it is neces-
sary to set up an opening between it and the adjacent
room, or to install mechanical ventilation which is inter-
locked with the leak detector.
(Total refrigerant charged amount: oz.)
(Min indoor volume where the indoor unit is installed: ft.
3
)
<
Limit density 0.3 (oz./ft.
3
)
The limit density of refrigerant which is used in this unit
is 0.3 oz./ft.
3
(ISO 5149).
The shipped outdoor unit comes charged with the
amount of refrigerant fixed for each type; so add it to
the amount that is charged at the field. (For the refriger-
ant charge amount at shipment, refer to the unit’s
nameplate.)
Minimum indoor volume & floor area relative to
the amount of refrigerant is roughly as given in
the following table.
07-115 SSHP_II 5/7/07 3:59 PM Page 15

Table of Contents

Related product manuals