Explanation of symbols
Distribution joint
(APR:
purchased separately
)
Solidly welded shut
(pinch weld)
Balance tubing
(ø
1/4"
)
Ball valve (field supply)
T-joint (field supply)
L5
LO
LA
LF
LM
LB LC
L2
L4
LG
LD L3
LH
Max.
1.3 ft
Max.
1.3 ft
For
extension
For
extension
H2
H3
H1
L1
2
3
1
5
4
AB
C
38
39
40
Table 1-2 Ranges that Apply to Refrigerant Tubing Lengths and to Differences in Installation Heights
Item Mark Contents Length(ft.)
Allowable tubing
length
L1 Max. tubing length
Actual length
492
Equivalent length 574
L (L2 – L4)
Difference between max. length and min.
length from the No.1 distribution joint
131
LM Max. length of main tubing (at max. diameter)
262*³
1, 2~ 40 Max. length of each distribution tube 98
L1 + 1 + 2~ 39 + A
+
B + LF + LG + LH
Total max. tubing length including length of each distribution
tube (only liquid tubing)
984
L5 Distance between outdoor units
32
Allowable elevation
difference
H1
When outdoor unit is installed higher than indoor unit 164
When outdoor unit is installed lower than indoor unit 131
H2 Max. difference between indoor units 49
H3 Max. difference between outdoor units
13
Allowable length of
joint tubing
L3
T-joint tubing (field-supply); Max. tubing length between the
first T-joint and solidly welded-shut end point
6.6
L = Length, H = Height
R410A distribution joint
APR-CHP680BA (for outdoor unit)
APR-CHP1350BA (for outdoor unit)
APR-P160BA (for indoor unit)
APR-P680BA (for indoor unit)
APR-P1350BA (for indoor unit)
1. Main tubing length LM = LA + LB … 262 ft
2. Main distribution tubes LC – LH are selected according to the capacity after the distribution joint.
3.
4. Sizes of indoor unit connection tubing 1 – 40 are determined by the connection tubing sizes on the indoor units.
The outdoor connection main tubing (LO portion) is determined by the total capacity of the outdoor units that are
connected to the tube ends.
Select the installation location so that the length and size of refrigerant tubing are within the allowable range shown in the figure below.
Do not use commercially available T-joints for the liquid tubing and parts.
* Be sure to use special R410A distribution joints (APR:
purchased separately
) for outdoor unit connections and tubing branches.
NOTE
1-5. Tubing Length
1: The outdoor connection main tubing (LO portion) is determined by the total capacity of the outdoor units that are connected to
the tube ends.
2: If the longest tubing length (L1) exceeds 295 ft. (equivalent length), increase the sizes of the main tubes (LM) by 1 rank for gas
tubes and liquid tubes. (Use a field supply reducer.) (Select the tube size from the table of main tube sizes (Table 1-3) on the
following page (LA table), and from the table of refrigerant tubing sizes (Table 1-8) on the second following page.)
3: If the longest main tube length (LM) exceeds 164 ft., increase the main tube size at the portion before 164 ft. by 1 rank for the
gas tubes. (Use a field supply reducer.)
(For the portion that exceeds 164 ft., set based on the main tube sizes (LA) listed in the table on the following page.)
4: If the size of the existing tubing is already larger than the standard tubing size, it is not necessary to further increase the size.
* If the existing tubing is used, and the amount of on-site additional refrigerant charge exceeds the value listed below, then
change the size of the tubing to reduce the amount of refrigerant.
Max. additional charge for 1 outdoor unit: 62 lbs
Max. additional charge for 2 outdoor units: 111lbs
NOTE
8