– 38 –
SM830079
11. SERVICE PROCEDURES
6) Outdoor Fan does not Run.
• Check resistance of fan
motor winding.
• Check fan motor capacitor
OK
• Check continuity between
terminals on the compressor
motor magnetic contactor.
• Check fan rotation.
Rotate the fan gently once
or twice by hand.
0633_X_S
• Check fan casing
for foreign matter
on the inside.
Remove foreign
matter or repair.
Repair or replace.
Fan cannot
be rotated.
Fan motor burnout
or foreign matter
in bearing.
7) Outdoor Fan does not Run for CL1852.
• Check fuse on PCB Ass’y in
outdoor unit for continuity.
• Check resistance of primary
winding of transformer. (TR)
1038_X_S
If fuse blows,
8) Compressor does not Run.
• Check compressor motor capacitor
(RC1).
Wait for 30 minutes until com-
pressor has cooled.
Compressor runs.
Compressor internal thermal
protector is operated.
• Check power supply voltage.
Is voltage abnormally low?
NO
• Is outdoor heat exchanger coil dirty
or are there obstacles near air
suction inlet?
• Check resistance of compressor
motor winding.
1336_X_S
OK