NOTE
< Combinations of operatable indoor units >
CLM2472
(Rated cooling capacity at 230V: 25400 BTU/h)
Voltage Rating : 230V 60Hz
7500 : KMS0772
9000 : KMS0972
11900 : KMS1272
17500 : KMS1872
24200 : KMS2472
-2-
The table lists the wall-mounted type of indoor units as representative models.
Room Room Room Room
ABCDCapacity ( Min.
-
Max. )
7500 = 7500 7500 7500 ( 4700
-
8800 )
9000
=
9000 9000 9000
(
4700
-
10900
)
11900
=
11900 11900 11900
(
5100
-
12200
)
17500
=
17500 17500 17500
(
5400
-
19700
)
24200
=
24200 23200 23200 ( 5400
-
23200 )
7500 + 7500
=
15000 7500 7500 15000
(
6800
-
17400
)
7500 + 9000
=
16500 7485 9015 16500
(
6800
-
19700
)
7500 + 11900
=
19400 7488 11912 19400
(
6800
-
22800
)
7500 + 17500
=
25000 7124 16676 23800
(
7100
-
25200
)
7500 + 24200
=
31700 6009 19391 25400
(
7100
-
25400
)
9000 + 9000
=
18000 9000 9000 18000
(
6800
-
21400
)
9000 + 11900
=
20900 8876 11724 20600
(
6800
-
23200
)
9000 + 17500
=
26500 8494 16506 25000
(
7100
-
25400
)
9000 + 24200
=
33200 6904 18496 25400
(
7100
-
25400
)
11900 + 11900
=
23800 11400 11400 22800
(
6800
-
24800
)
11900 + 17500
=
29400 10277 15123 25400
(
7100
-
25400
)
11900 + 24200
=
36100 8387 17013 25400
(
7100
-
25400
)
17500 + 17500
=
35000 12700 12700 25400 ( 7100
-
25400 )
7500 + 7500 + 7500
=
22500 7333 7333 7333 22000
(
8500
-
25400
)
7500 + 7500 + 9000
=
24000 7177 7177 8645 23000
(
9800
-
25400
)
7500 + 7500 + 11900
=
26900 7073 7073 11253 25400
(
9800
-
25400
)
7500 + 7500 + 17500
=
32500 5851 5851 13697 25400
(
9800
-
25400
)
7500 + 9000 + 9000
=
25500 7099 8551 8551 24200
(
9800
-
25400
)
7500 + 9000 + 11900
=
28400 6692 8061 10647 25400
(
9800
-
25400
)
7500 + 9000 + 17500
=
34000 5588 6731 13081 25400
(
9800
-
25400
)
7500 + 11900 + 11900
=
31300 6074 9663 9663 25400
(
9800
-
25400
)
7500 + 11900 + 17500
=
36900 5150 8194 12056 25400
(
9800
-
25400
)
9000 + 9000 + 9000
=
27000 8467 8467 8467 25400
(
9800
-
25400
)
9000 + 9000 + 11900
=
29900 7649 7649 10102 25400
(
9800
-
25400
)
9000 + 9000 + 17500
=
35500 6441 6441 12518 25400
(
9800
-
25400
)
9000 + 11900 + 11900
=
32800 6975 9212 9212 25400
(
9800
-
25400
)
9000 + 11900 + 17500
=
38400 5957 7867 11576 25400
(
9800
-
25400
)
11900 + 11900 + 11900
=
35700 8467 8467 8467 25400
(
9800
-
25400
)
11900 + 11900 + 17500
=
41300 7317 7317 10766 25400 ( 9800
-
25400 )
Single-room
Operation
4-room
Operation
2-room
Operation
3-room
Operation
COOLING
Indoor Unit Capacity (BTU/h)
Indoor Unit Combination
Total Performance
(Concurrent operation of 4 indoor units prohibited)
This multi outdoor unit allows up to four indoor units to be connected.
However, all four indoor units must not be operated concurrently.
Otherwise, the air conditioner may not run properly.
Up to three indoor units may be operated concurrently.
IMPORTANT!
Table 1