19
F26 * Display of actual operation rate
F27 * Display of calculated running rate
F28 * Display of delay time of permission for measuring running rate (2 hrs timer)
F29 * Display of delay time of permission for measuring running rate (8 hrs timer)
F30 * ROM version is displayed
F31 * Filter alarm
F32 Display of condensing fan motor accumulating time
F33~F39 Unused
Setting
procedure:
In PV display, keep pressing key over 5seconds to display “F00”.
Input the desired function code with key and key.
Press SET key to be function mode available.
* … You should input service code in F06 beforehand.
To cancel service code, input “000” in F06 or turn the power off.
F00: <Purpose> Simply passing through if entered by mistake.
<Operation> Press SET key in “F00” displayed to revert to PV display.
F01: <Purpose> SV
H
(high temp. alarm SV) setting
<Operation> Input F01 and press SET key to display “010” (initial value).
Set the value in the range “005”~“020” with key. Press SET key
to store the value and revert to PV display.
F02: <Purpose> SV
L
(low temp. alarm SV) setting
<Operation> Input F02 and press SET key to display “-10” (initial value).
Set the value in the range “-05”~“-20” with key. Press SET key to
store the value and revert to PV display.
F03: <Purpose> Battery accumulating time is displayed
<Operation> Input F03 and press SET key to display alternately F03 with “00.0”
(in case battery used for a month or less). Press SET key to revert to
PV display.
F04: <Purpose> Door alarm delay time is set
<Operation> Press SET key in “F04” displayed to display ‘002’ (initial setting).
Change your desired value among ‘001’~’015’ with key and
key and press SET key to store the value and revert to PV
display.
F05: <Purpose> Compressor (H) / (L) is turned on with forcibly delayed (by minute
increment) when the power retrieves from the power failure.
<Operation> Input “F05” and press SET key to display “002” (initial).
Change the value in the range “002”~”015” with key and key.
Press SET key to store the value and revert to PV display.
F06: <Purpose> Dividing F-code for customer used from service
<Operation> Input F06 and press SET key to display “000” (initial value).
Set to “384” with key and key. Press SET key to store the
value and revert to PV display.
<Cancel> Input F06 and press SET key to display “384”.
Change to “000” with key and key. Press SET key to store
the value and revert to PV display.
Turn the power off then on to revert to “000”. (not stored in
non-volatile memory)
Note) “384” is storied in non-volatile memory during battery back-up.
(battery SW is ON)
F07: <Purpose> To match temperature of temp. sensor with temperature of center at
the chamber.
<Operation> Input service code in F06 prior to use this mode.
Input F07 and press SET key to display “00.0” (initial value).