1-7. Straight Equivalent Length of Joints
Design the tubing system by referring to the following table for the straight equivalent length of joints.
Table 1-8 Straight Equivalent Length of Joints
Table 1-9 Refrigerant tubing (Existing tubing can be used.)
Tubing size (in. (mm))
Material O Material 1/2H • H
ø1/4" (ø6.35) t1/32 (t0.8)
ø3/8" (ø9.52) t1/32 (t0.8) ø1-1/8" (ø28.58) t5/128 (t1.0)
ø1/2" (ø12.7) t1/32 (t0.8) ø1-1/4" (ø31.75) t3/64 (t1.1)
ø5/8" (ø15.88) t5/128 (t1.0) ø1-1/2" (ø38.10) over t3/64 (t1.15)
ø3/4" (ø19.05)
over t5/128 (t1.0)
ø1-5/8" (ø41.28) over t3/64 (t1.20)
ø7/8" (ø22.22) t5/128 (t1.0)
* When bending the tubes, use a bending
radius that is at least 4 times the outer
diameter of the tubes.
In addition, take sufficient care to avoid
crushing or damaging the tubes when
bending them.
1-8. Additional Refrigerant Charge
Additional refrigerant charge amount is calculated from the liquid tubing total length and a type of outdoor unit as follows.
Required amount of additional refrigerant charge =
[ (Amount of additional refrigerant charge per ft. of
each size of liquid tube × its tube length) + (...) + (...)]
+ [(Necessary amount of additional refrigerant charge
per outdoor unit + (...) + (...)]
* Always charge accurately using a scale for weighing.
*1: For the solenoid valve kits, use type 160 with parallel specifications. Branch the tubing before and after the solenoid valve kits.
Table 1-7 Indoor Unit Tubing Connection Size ( 1 40)
Unit: in. (mm)
Distribution
joint-solenoid
valve kit tubing
Solenoid valve
kit-Indoor
unit tubing
connection
Discharge tubing
Liquid tubing
Suction tubing
Indoor unit type
Total system horsepower
7 9 12 15 18 19 24 36 48 54
0.8 1 1.3 1.7 2 2.1 3 4 5 5.5
o5/8" (o15.88)
o1/2" (o12.7)
o3/8" (o9.52)
Gas tubing
Liquid tubing
o1/2" (o12.7)
o1/4" (o6.35)
o5/8" (o15.88)
o3/8" (o9.52)
Table 1-10-1 Amount of Refrigerant Charge Per ft.,
According to Liquid Tubing Size
Liquid tubing
size
ø1/4"
(ø6.35)
ø3/8"
(ø9.52)
ø1/2"
(ø12.7)
ø5/8"
(ø15.88)
ø3/4"
(ø19.05)
ø7/8"
(ø22.22)
Amount of
refrigerant
charge (oz/ft.)
0.279 0.602 1.38 1.99 2.78 3.93
Table 1-6 Refrigerant Charge Amount at Shipment (for outdoor unit)
DC
CHDZ07263 CHDZ09663
CHDZR07263 CHDZR09663
(oz)
416 416
W-3WAYECO-iU.indb10W-3WAYECO-iU.indb10 2009/11/1318:09:262009/11/1318:09:26