P.C.Board
Circuit Fuse
Controls
Part No.
Microprocessor
400V 3.15A
CB-CMRV3656EH
Control P.C.B
-
250V 25A
POW-CMRV3656EH-B1
Noise Filter P.C.B
-
-
POW-CMRV3656EH-C1
H.I.C.Board
1 ... D490
Propeller
DC Motor
SIC-71FW-D881-1 ... 1
8
-
81
750 / 700
Internal Controller
Yes
Yes
-
-
Aluminum Plate Fin / Copper Tube
2
1.2
0.792
Fan
Q'ty ... Dia.
Type
mm
Fan Motor
Nominal Output
Coil Resistance
Rough Measure RPM (Cool:Hi / Heat:Hi)
Type
Model ... Q'ty
No. of Poles
Safety Device
Type
Over- Current Protection
Over- Heat Protection
(Ambient Temp. 20 °C)
Run Capacitor Micro F
VAC
W
Ohm
Face Area
Coil
Rows
Fin Pitch
Heat Exchanger Coil
m
2
mm
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
2-2. Major Component Specifications
2-2-1. Outdoor Unit
Outdoor Unit SAP-CMRV3656EH
C-9RVN273H0H / 2,700W
DC Twin Rotary (Hermetic)
Compressor
Compressor Model / Nominal Output
Type
FV68S ... 1,400Compressor Oil ... Amount CC
T - R : 0.169Coil Resistance (Ambient Temp. 25 °C) Ohm
T - S : 0.169
R - S : 0.169
Safety Device
YesCT (Peak current cut-off control)
YesCompressor Discharge Temp. Control
Yes
Operation cut-off control in abnormal ambient Temp.
CS-7LOverload Relay
Open : 115 °C, Close : 100 °C
Model
Operation Temp.
-Run Capacitor
-
Micro F
VAC
230V 25WCrankcase Heater
Acrylic baked-on enamel finishExternal Finish