Indoor Unit SAP-K127RAX
Outdoor Unit SAP-C127RAX
230 V Single Phase 50 Hz
TC : Total Cooling Capacity (kW)
SHC : Sensible Heat Capacity (kW)
CM : Compressor Input (kW)
Rating conditions (#Mark) are
Outdoor Ambient Temp. 35 °C D.B.
Indoor Unit Entering Air Temp. 27 °C D.B. / 19 °C W.B.
28
RATING CAPACITY 3.55 kW
AIR FLOW RATE 460
m
3
/h
EVAPORATOR CONDENSER
ENT. TEMP.
o
C OUTDOOR AMBIENT TEMP.
o
C
W.B. D.B. 20 25 30 35 40 43
TC 3.58 3.42 3.27 3.11 2.92 2.69
CM 0.92 1.00 1.07 1.15 1.33 1.51
21 SHC 2.34 2.25 2.16 2.08 1.98 1.86
15 23 SHC 2.57 2.49 2.40 2.31 2.21 2.10
25 SHC 2.81 2.72 2.64 2.55 2.45 2.33
27 SHC 3.05 2.96 2.87 2.79 2.69 2.57
29 SHC 3.29 3.20 3.11 3.03 2.92 2.69
31 SHC 3.52 3.42 3.27 3.11 2.92 2.69
TC 3.84 3.67 3.50 3.34 3.14 2.89
CM 0.95 1.03 1.10 1.18 1.36 1.54
21 SHC 2.10 2.01 1.92 1.83 1.74 1.61
17 23 SHC 2.33 2.24 2.16 2.07 1.97 1.85
25 SHC 2.57 2.48 2.40 2.31 2.21 2.09
27 SHC 2.81 2.72 2.63 2.55 2.45 2.33
29 SHC 3.05 2.96 2.87 2.79 2.69 2.57
31 SHC 3.28 3.20 3.11 3.02 2.92 2.80
TC 4.08 3.91 3.73 # 3.55 3.34 3.07
CM 0.98 1.06 1.13 1.22 1.40 1.58
21 SHC 1.84 1.75 1.66 1.58 1.48 1.36
19 23 SHC 2.07 1.99 1.90 1.81 1.72 1.60
25 SHC 2.31 2.22 2.14 2.05 1.95 1.83
27 SHC 2.55 2.46 2.37 2.29 2.19 2.07
29 SHC 2.79 2.70 2.61 2.53 2.43 2.31
31 SHC 3.02 2.94 2.85 2.77 2.67 2.55
TC 4.33 4.14 3.95 3.76 3.54 3.25
CM 1.01 1.09 1.16 1.25 1.44 1.62
23 SHC 1.81 1.72 1.64 1.55 1.46 1.34
21 25 SHC 2.05 1.96 1.87 1.79 1.69 1.58
27 SHC 2.28 2.20 2.11 2.03 1.93 1.81
29 SHC 2.52 2.43 2.35 2.27 2.17 2.05
31 SHC 2.76 2.67 2.59 2.50 2.41 2.29
TC 4.59 4.39 4.19 3.95 3.70 3.44
CM 1.03 1.12 1.19 1.28 1.47 1.66
23 25 SHC 1.76 1.68 1.59 1.50 1.40 1.30
27 SHC 2.00 1.92 1.83 1.73 1.63 1.53
29 SHC 2.24 2.15 2.07 1.97 1.87 1.77
31 SHC 2.48 2.39 2.30 2.21 2.11 2.01