Control PCB
Control Circuit Fuse
Controls
Part No.
Microprocessor
250V 25A
CB-CMRV1926EH
1 ... D460
Propeller
DC Motor
SIC-71FW-D490-1 ... 1
8
-
90
650 / 650
Internal Controller
Yes
-
-
Aluminum Plate Fin / Copper Tube
2
1.4
0.595
Fan
Q'ty ... Dia.
Type
mm
Fan Motor
Nominal Output
Coil Resistance
Rough Measure RPM (Cool:Hi / Heat:Hi)
Type
Model ... Q'ty
No. of Poles
Safety Device
Type
Over- Current Protection
Yes
Over- Heat Protection
(Ambient Temp. 20 °C)
Run Capacitor Micro F
VAC
W
Ohm
Face Area
Coil
Rows
Fin Pitch
Heat Exchanger Coil
m
2
mm
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Outdoor Unit SAP-CMRV1926EH
5KD240XAB21 / 1,700W
DC Twin Rotary (Hermetic)
Compressor
Compressor Model / Nominal Output
Type
FV50S ... 900Compressor Oil ... Amount CC
U - V : 0.720Coil Resistance (Ambient Temp. 20 °C) Ohm
V - W : 0.708
W - U : 0.726
Safety Device
YesCT (Peak current cut-off control)
YesCompressor Discharge Temp. Control
Yes
Operation cut-off control in abnormal ambient Temp.
CS-7LN115Overload Relay
Open : 115 °C, Close : 100 °C
Model
Operation Temp.
-Run Capacitor
-
Micro F
VAC
230V 25WCrankcase Heater
Acrylic baked-on enamel finishExternal Finish
13