5
All outputs are equipped with protection for inductive loads and pulse interference.
Assignment of the particular outputs can be restricted to the specific partitions / zones of the
system.
For each output can be defined the operation time in seconds (from 1 to 99 seconds), in
minutes (from 1 to 99 minutes), or LATCH type (until switch off). It is possible to determine
the output polarity for active state (+12V or 0V on the load), and whether it should operate in
pulsed or continuous mode.
Designation of the outputs can be adapted to the needs of the alarm system controlled by the
panel. Though individual outputs differ by their design, each of them can perform one of the
following functions:
00 - not used - remains inactive from the power-up, according to the setting of "polarity"
option.
01 - burglary - the output starts on detecting a burglary alarm by the control panel. The
alarm is triggered by armed zones, zones tamper circuits, keypads tamper
contacts, and by the user (through the ALARM PANIC function). If the zones to
which the output is to react are defined, the zone alarms will be limited to those
included in the "list of zones" (the other alarms will be effected irrespective of the
source). It is also possible to indicate (in the output options) the partition the output
is associated with. If this is the case, the zone alarms will be limited to those from
the zones belonging to the chosen partition. When the "list of zones" is empty and
there are no chosen partitions, the output reacts to all alarms (except for the fire
alarms).
The output can remain active for a specified time (from 01 to 99 seconds or from
01 to 99 minutes) or until the alarm is cleared by the user. During its operation, it
can every second change its state (pulsate).
02 - fire/burglary - the output starts on detecting by the control panel of a burglary alarm
(continuous signal) and/or a fire alarm (intermittent signal). The output operation
can be limited to the indicated "list of zones" or a specific partition (identically as
for the 01 output type). The output can remain active for a specified time (from 01
to 99 seconds or from 01 to 99 minutes) or until the alarm is cleared by the user.
03 - fire - the output starts when the control panel detects a fire alarm. Such an alarm is
triggered by fire zones or the user (through the ALARM FIRE function). The output
operation can be limited to the specified "list of zones" or particular partitions
(identically as for the 01 output type). There is no sense to choose any other
zones than the fire ones, as they would not generate a fire alarm. The output can
remain active for a specified time (from 01 to 99 seconds or from 01 to 99 minutes)
or until the alarm is cleared by the user. During operation, it can every second
change its state (pulsate).
04 - keypad alarms - the output starts on detecting any keypad alarm. The output can
remain active for a specified time (from 01 to 99 seconds or from 01 to 99 minutes)
or until the alarm is cleared by the user. During its operation, it can every second
change its state (pulsate).
05 - keypad fire alarm - the output starts on triggering the fire alarm by the user (with the
FIRE ALARM function). The output can remain active for a specified time (from 01
to 99 seconds or from 01 to 99 minutes) or until the alarm is cleared by the user.
During operation, it can every second change its state (pulsate).
06 - keypad panic alarm - the output starts on triggering the PANIC alarm by the user. The
output can remain active for a specified time (from 01 to 99 seconds or from 01 to
99 minutes) or until the alarm is cleared by the user. During operation, it can every
second change its state (pulsate).