EasyManua.ls Logo

Saunders M-VUE - Troubleshooting Alarms; Alarm 1: Unexpected Position Change; Alarm 2: Stroke Out of Range; Alarm 3: Stop at the Middle of the Way

Saunders M-VUE
32 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
30
www.cranecpe.com
Crane ChemPharma & Energy
Troubleshooting Alarms
M-VUE can display three alarms:
Alarm 1: Unexpected position change
Alarm 2: Stroke out of range
Alarm 3: Stop at the middle of the way
Alarm 1: This alarm indicates that an
unexpected position change has occurred. P1
flashes red to indicate Alarm 1. The alarm will
correct itself after the fault has been cleared
Check if the aseptic valve operates correctly
Check air connectors and required pressure
Alarm 2: Indicates that the actuator shaft has
traveled over or under the values stored during
initial calibration. P2 will flash red to indicate the
alarm (± 20% tolerance)
Check for actuator damage
Perform Self-Calibration again
Alarm 3: Indicates that the actuator shaft has
not reached the desired position after the initial
position has been detected. P3 will flash red to
indicate the feedback sensor status Position 1
(Open) and Position 2 (Closed) are 0.
Check for actuator damage
Verify correct pressure supplied to the actuator
Normal
Condition
Not Expected
Position
Alarm (P1)
Condition
Note: To disable any LED alarm hold two magnetics keys over H1 and H2 for 6 seconds. The corresponding LED alarm will stop
Flashing. The generated alarm remains in the register and can be viewed over a bus network or by holding two magnetics keys
over H1 and H2 for 6 seconds