ADDENDUM B
Appendix B shows the change log of firmware and software releases for RGDAT-A70 compliant with
technical specification GSTP001 by ENEL.
Changes to firmware RGDAT-A70
Release 2.00
First official release (ENEL approval according to technical specification GSTP001)
Release 2.01
Changes in functionalities for Endesa (Request by ENEL)
Other minor changes
Release 2.02
Increase the maximum value of the threshold 51N to 600 A (Request by ENEL)
8
Improvements in Io pre-fault compensation current calculation (for Outdoor version, with TATVs)
Release 2.10
9
Io prefault compensation is now used for all configurations with 3 phase current sensors
Io prefault current is calculated using data 100 ms earlier than the actual ones
Add support to fix issues with some lots of Altea combined sensors
Changes to software RGDAT-A70
Release 2.00
10
First official release (ENEL approval according to technical specification GSTP001)
Release 2.01
11
In the dialog box of "Firmware Update" procedure, it was added the option of choosing the firmware
version to use, selecting it from the ones released so far (Request by ENEL)
All the firmware version released so far (from 1.00 until 2.01) are added to the installation program
(Request by ENEL)
P515D851 Rev. E November 2019 Pag. 44 of 45
8
In case of firmware update of RGDAT-A70 with release firmware 1.xx, the function is available only if the
RGDAT-A70 is equipped with Rogowski coil current sensors or TATVs
9
If the RGDAT-A70 firmware is updated to the version indicated, at the end of the update it is necessary to give
also the "Default data" command and then reconfigure the device with the data related to the plant in which it is
installed
10
The release 2.00 of the software is compatible also with previous model of RGDAT-A70, with firmware release
1.xx
11
With the changes introduced with this release, the software RGDAT-A70 with release 1.xx will not be updated
and will be discontinued. Any actions that may be relevant to the old firmware and software versions will be
implemented directly in the software 2.xx, which will have to ensure compatibility with RGDAT-A70 with firmware
1.xx also in the future