7.8.4 Earth fault supervision
Warn or trip of I
E
> element
0.1 (1...5)
0.2 (5...10)
0.5 (10...20)
1 (20...50)
2 (50...100)
5 (100...200)
3% of the set value
or. 0.3% I
N
0.04 - 300 s (EXIT)
(definite time)
0.02 (0.06...1.0)
0.05 (1.0...2.0)
0.1 (2.0...5.0)
0.2 (5.0...8.5)
0.5 (10...20)
1,0 (20...50)
2.0 (50...100)
5.0 (100...200)
10.0 (200...300)
Normal Inverse Typ “A”
Very Inverse Typ “B”
Extremely Inverse Typ “C”
RI - Inverse
Long Time Inverse
RXIDG-Kennlinie
NINV
VINV
EINV
RINV
LINV
RXID
0,05 - 10 (EXIT)
0.05 – 1.0 (EXIT) only RXIDG
(inverse time)
0.01 (0.05...0.5)
0.02 (0.5...1.0)
0.05 (1.0...2.0)
0.1 (2.0...5.0)
0.2 (5.0...10.0)
3% related to the measured
current value and 20ms re-
spectively
(see EN 60255-3)
Reset Mode for tripping times
0,1 (1...5)
0,2 (5...10)
0,5 (10...20)
1 (20...50)
2 (50...100)
5 (100...200)
10 (200...400)
0.02 (0.06...0.5)
0.05 (0.5...2.0)
0.1 (2.0...5.0)
0.2 (5.0...10)
0.5 (10...20)
1.0 (20...50)
2.0 (50...100)
5.0 (100...200)
10.0 (200...300)
Table 7.4: Earth fault supervision
* Tripping time in forward direction (tripping range)
** Tripping time in backward direction (blocking range), see chapter 4.7.3