EasyManua.ls Logo

Sel 651RA - Wiring With Fuse Block; Form Drip Loop and Route Harness Wires; Prepare and Attach Harness Wires

Sel 651RA
8 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SEL-651RA Recloser Control Date Code 20160329
4
Wiring With Fuse
Block
Step 1. Form a drip loop and route the harness wires to the bottom of
the fuse block for field wiring. See Figure 5.
Figure 5 Route Harness Wires to Bottom of Fuse Block
Step 2. Cut the cables to a reasonable length, remove about 2 inches of
the jacket, and strip the individual wires about 7/16 of an inch.
Step 3. The Z-side cable is marked with white heat shrink on the Z-side
ring terminals to distinguish them from the Y-side ring
terminals. Mark the end of the Z-side wires (wires from where
the heat shrunk ring terminals were cut) for future reference.
Step 4. Attach the 8-pin harness wires according to the table in
Figure 6 as required for your specific secondary input voltage
option. See Table 1 for SIV-specific wiring.

Related product manuals