Service parameters S1
Service parameters S1 are intended for DD2+ service settings. To change the
selected parameter, hold key for approximately 5 seconds. Parameter
starts to flash. Press key or to set the parameter value. To store the setted
value, again hold key for approximately 5 seconds. In service parameters
S1 are the following settings; (factory settings):
- [S1.1] measured temperatures roundup
(0.1 °C, 0.2 °C, 0.5 °C, 1.0 °C); (0.5 °C)
- [S1.2] room temperature
(- - - no sensor, 1 - built in sensor, 2 - auxiliary sensor,
3 - avg. of built in and auxiliary sensor); (1)
- [S1.3] menu auto-exit (1 - 20 s, 2 - 200 s); (1)
- [S1.4] room unit locking (- - - no locking, 1 - no locking, but limited
function of key , 2 - enabled key Party and knob,
3 - enabled only key Party, 4 - full lock,
5 - room temperature sensor influence is disabled for at
least 5 hours); (2)
- [S1.5] max. scale for day temperature setting
(10 °C ÷ 40 °C); (30 °C)
- [S1.6] min. scale for day temperature setting
(0 °C ÷ 40 °C); (10 °C)
Service parameters S3
Service parameters S3 are intended for DD2+ service settings. To change the
selected parameter, hold key for approximately 5 seconds. Parameter
starts to flash. Press key or to set the parameter value. To store the
setted value, again hold key for approximately 5 seconds. In service
parameters S3 are the following settings; (factory settings):
- [S3.1] Parameter locking
(- - - no locking, 1 - locked are groups S,
2 - locked are parameters S and P,
3 - locked complete menu); (1)