www.sentera.eu
MIW-EVS-DM-EN-000 - 14 / 03 / 2016 12 - 16
back to the table of contents
MODBUS REGISTER MAPS
INPUT REGISTERS
Data type Description Data Values
1 Analogue input level unsigned int. Analogue input value depending on the selected analogue input type. 0 —100
0 =
100 =
0 =
100 =
0 VDC
10,0 VDC
or
0 mA
20,0 mA
2 Current output voltage unsigned int. Actual output voltage
0
30—100
0 =
30 =
100 =
0 % Us
30 % Us
100 % Us
3 Analogue input type unsigned int. Type of the selected analogue input 0—1
0 =
1 =
0—20
mA
0—10 VDC
4
Ascending/descending
input mode
unsigned int.
Ascending or descending analogue input mode depending on the selected
analogue input type.
0—1
0 =
1 =
0 =
1 =
10—0 VDC
0—10 VDC
or
20—0 mA
0—20 mA
5 Maximum output voltage unsigned int. Maximum output voltage 75—100
75 =
100 =
75 % Us
100 % Us
6 Minimum output voltage unsigned int. Minimum output voltage 30—70
30 =
70 =
30 % Us
70 % Us
7 Enable off level unsigned int. Enables off level 0—1
0 =
1 =
Disabled
Enabled
8 Off level value unsigned int.
Off level value depending on the selected analogue input type and
ascending/descending analogue input mode.
0— 40
60—100
Ascending mode:
0 =
400 =
0 =
200 =
Voltage
0 VDC
4,0 VDC
Current
0 mA
8,0 mA
Descending mode:
100 =
60 =
100 =
60 =
Voltage
10,0 VDC
6,0 VDC
Current
20,0 mA
12,0 m A
9 Kick start/soft start unsigned int. Selects kick start or soft start 0—1
0 =
1 =
soft start
kick start
10 Remote control input unsigned int. Remote control input 0—1
0 =
1 =
Disabled
Enabled
12 L1 control unsigned int. L1 control 0—1
0 =
1 =
Off
On
14 ON/Stand-by LED unsigned int. ON/Stand-by LED 0—2
0 =
1 =
2 =
Off
On
Stand-by
15-20 Reserved, returns 0
EVS
ELECTRONIC FAN SPEED
POWER MODULE WITH MODBUS RTU