Holding register 16 (40016) defines the OFF level. e default value is ‘0’ (0 VDC).
is value depends on the selected analogue input type and mode. e register
values vary in the ranges of 0—40 (0 4,0 VDC) for ascending voltage signal and
60—100 (6,0— 10,0 VDC) for descending voltage signal. When current signal is
selected, the register values are in ranges of 0—40 (0—8,0 mA) for ascending
signal and 60100 (12,0—20,0 mA) for descending signal.
Holding register 17 (40017) sets kick start or soft start. e default value is ‘1
(kick start). ‘0’ value is for soft start
Holding register 18 (40018) contains kick start or soft start duration time.
e default value is ‘10’ (10 seconds). e register values vary from ‘0’ to ‘60’
(0—60 seconds). is setting is accessible only in Modbus mode.
Holding register 19 (40019) selects the remote control input functionality. e
default value is ‘0’ for normal mode. Value ‘1’ is for timer mode. is setting is
accessible only in Modbus mode. OFF level mode is not used in timer mode.
Holding register 20 (40020) selects the analogue input functionality. e default
value is ‘0’ for normal mode; ‘1’ is for logic mode. is setting is accessible only in
Modbus mode.
Holding register 21 (40021) sets the value of the operation timer. is holding
register is accessible only in timer mode and / or logic mode. e default value is
‘60’ (60 seconds). e register values can vary from 0 to 200 (0200 seconds).
is setting is accessible only in Modbus mode. e working time is equal to the
sum of the kick start / soft start duration time and the time value of the operation
timer. When a working time expires, only a remote control input or analogue input
can restart the unit.
e next holding registers 22 (40022)—30 (40030) are not used. ey are
readonly.
Holding register 31 (40031) overrides the output voltage value in Modbus mode
when output override is enabled. e override value setting does not depend on
the other settings except on the kick start or soft start selection. e default value
is ‘0’ (VAC). e register value can vary in the range of 30—100 (30—100 % Us).
It can be also ‘0’ (0 % Us).
e next holding registers 32 (40032)—40 (40040) are not used. ey are read
only
TRANSPORT AND STOCK KEEPING INFORMATION
Avoid shocks and extreme conditions; stock in original packing.
WARRANTY INFORMATION AND RESTRICTIONS
Two years from the delivery date against defects in manufacturing. Any modifications
or alterations to the product after the date of publication relieve the manufacturer
of any responsibilities. e manufacturer bears no responsibility for any misprints or
mistakes in this data.
MAINTENANCE
In normal conditions this product is maintenance-free. If soiled, clean with a dry or
dampish cloth. In case of heavy pollution, clean with a non-aggressive product. In
these circumstances the unit should be disconnected from the supply. Pay attention
that no fluids enter the unit. Only reconnect it to the supply when it is completelydry.