27 Jetflush Rapid
V1- 02-15
EN
Test 2: Flow rate test
What you need: Empty clean 5 litre container.
1. Repeat steps 17 of test above.
2. Hold the dump hose so that it will discharge water into the empty container.
3. When ready, use an assistant to time how long it takes to fill the 5 litre
container. You should get a reading of between 9–11 seconds.
Inspection
1. Remove the 4 bolts that connect the flange to the tank.
2. Lift and withdraw the pump assembly from the tank.
3. Inspect the rotor cover at the bottom of the unit to ensure:
It is flat.
There are no bolts damaged or missing.
The O-ring is still in place and has not been pushed out.
4. Inspect the inside of the impeller to make sure that there is no debris inside.
5. Check all hose connection to ensure they are secure.
Section C – Troubleshooting, Service & Repair
Jetflush Rapid Guidelines (19-02-15).indd 27 19/02/2015 12:13