EasyManuals Logo

SEP LEM012SD User Manual

SEP LEM012SD
11 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #4 background imageLoading...
Page #4 background image
4 SEP LEMO12SD / LEM012SS 2015
1.3 Performance criteria:
Operating humidity ≤ 75%
Storage humidity ≤ 95%
Operating temperature -10°C - +50°C
Storage temperature -30°C - +70°C
International standard IEC 62053-21
Accuracy class 1
Protection against penetration
of dust and water IP51
Insulating encased meter of
protective class
1.4 Specifications:
Nominal voltage (Un) 230V AC
Operational voltage 161 - 300V AC
Insulation capabilities:
- AC voltage withstand 2KV for 1 minute
- Impulse voltage withstand 6KV 1.2µS waveform
Basic current (Ib) 5 A
Maximum rated current (Imax) 32 A
Operational current range 0.25A - 32A
Over current withstand 960A for 0.01s
Operational frequency range 50Hz ±10%
Internal power consumption ≤2W / 10VA
Test output flash rate (Red LED) 2000 pulses per kWh (0.5Wh/imp)
Pulse output rate (pins 20 & 21) 2000 pulses per kWh (0.5Wh/imp)
Pulse supply current Ui max=27V Ii max 27mA
Power supply indicator (Green LED) Meter is connected and working OK
Consumption indicator (Red LED) Flashing at load running
Data display mode 7+1 digits for LCD display
(for the LEM012SS 5 +1digits for mechanical
display 5 integer 1 decimal.
Data save The data can be stored more than 20 years
when power cut.
Wire connection Up to 10mm2 stranded copper wire
1.5 Intrinsic errors:
0.05Ib Cosφ = 1 ±1.5%
0.1Ib Cosφ = 0.5L ±1.5%
Cosφ = 0.8C ±1.5%
0.1Ib - Imax Cosφ = 1 ±1.0%
0.2Ib - Imax Cosφ = 0.5L ±1.0%
Cosφ = 0.8C ±1.0%
1.Ib - Imax Cosφ = 1 ≤ 1%