3-3
AY-ZP35PR
Function Operation Self-diagnosis result 
display
Description Detection period Reset condition Indoor 
unit error 
display
Indoor unit Outdoor 
unit
29 PAM clock error When power source frequency
cannot be determined (at start-
up), or when power source clock 
cannot be detected for 1 contin-
uous second (at startup).
At compressor startup,
when in operation
Compressor continues
operation without stop-
ping.
None Yes Yes
ڏ
1—A single error judgment results in the display of the indoor unit error (complete shutdown).
ڏ
2—The outdoor unit restarts four times before the indoor unit error is displayed (complete shutdown).
ڏ
3—The outdoor unit restarts eight times before the indoor unit error is displayed (complete shutdown).
[2] AIR TO AIR HEAT PUMP OPERATION IN THERMISTOR ERROR
1. Indoor unit
Item Mode Control opera-
tion
When resistance 
is low (tempera-
ture judged high-
er than actual)
Short-circuit When resistance 
is high (tempera-
ture judged lower 
than actual)
Open-circuit
Room temperature 
thermistor (TH1)
Auto Operation mode 
judgment
Cooling mode is ac-
tivated even if room 
temperature is low.
Cooling mode is acti-
vated in most cases.
Heating mode is ac-
tivated even if room 
temperature is high.
Heating mode is 
always activated.
Cooling Frequency control Room becomes too 
cold.
Air/air heat pump 
operates in full 
power even when 
set temperature is 
reached.
Room does not 
become cool.
Compressor does 
not operate.
Dehumidifying Room temperature 
memory
Frequency control
Normal operation. Room temperature 
is stored in memo-
ry as 31.0°C, and 
compressor does 
not stop.
Normal operation. Room temperature 
is stored in memo-
ry as 18.5°C, and 
compressor does 
not operate.
Heating Frequency control Room does not 
become warm.
Hot keep status 
results immediate-
ly after operation 
starts.
Frequency does not 
increase above 30 
Hz (40 Hz).
Room becomes too 
warm.
Air/air heat pump 
operates in full 
power even when 
set temperature is 
reached.
Heat exchanger 
thermistor (TH2)
Cooling
Dehumidifying
Freeze prevention Indoor unit evapora-
tor may freeze.
Indoor unit evapora-
tor may freeze.
Compressor stops 
occasionally.
Compressor does 
not operate.
Heating Cold air prevention Cold air prevention 
deactivates too soon 
and cold air dis-
charges.
Compressor oper-
ates at low speed or 
stops, and frequency
does not increase.
Cold air prevention 
deactivates too slow.
Cold air prevention 
does not deactivate, 
and indoor unit fan 
does not rotate.