3-17
AY-ZP35PR
Indoor and 
outdoor units 
do not oper-
ate.
7-time
Timer (Orange) 7 0 Outdoor unit
AC Current
AC over current 
error
(1) Check the outdoor 
unit air outlet for 
blockage.
(1) Ensure unob-
structed air flow 
from the outdoor 
unit air outlet.
Operation (Green)
Plasmacluster 
(Blue)
(2) Check the outdoor 
unit fan for proper 
rotation.
(2) Check the outdoor 
unit fan motor.
Timer (Orange) 1 AC current error 
when OFF
(1) IPM continuity check (1) Replace the out-
door IPM PWB
Operation (Green)
Plasmacluster 
(Blue)
Timer (Orange) 2 AC maximum 
current error
(1) Check the outdoor 
unit air outlet for 
blockage.
(1) Ensure unob-
structed air flow 
from the outdoor 
unit air outlet.
Operation (Green)
Plasmacluster 
(Blue)
(2) Check the outdoor 
unit fan for proper 
rotation.
(2) Check the outdoor 
unit fan motor.
Timer (Orange) 3 AC current defi-
ciency error
(1) Check if there is an 
open-circuit in the 
secondary winding 
of the current trans-
former of the outdoor 
unit control PWB.
(1) Replace the out-
door unit control 
PWB assembly.
Operation (Green)
Plasmacluster 
(Blue)
(2) Check if the refriger-
ant volume is abnor-
mally low.
(2) Charge the speci-
fied amount of 
refrigerant.
(3) Check if the refriger-
ant flows properly.
(3) Correct refrigerant 
clogs. (Stop valve, 
pipe, expansion 
valve)
Indoor and 
outdoor units 
do not oper-
ate.
8-time
Timer (Orange) 8 0 Abnormal 
wire check
Abnormal wire 
check error
(1) Check the expansion 
valve. (unit A - C)
(1) Replace the out-
door control board 
assembly.
Operation (Green)
Plasmacluster 
(Blue)
(2) Are four expansion 
valves connected by 
mistake 
(2) Reattach
(3) Check the wiring 
between units.
(3) Check the wiring 
between units.
Problem 
symptom
Outdoor 
unit indi-
cation 
(LED1)
Indoor unit Malfunc-
tion No.
Content of diagnosis Check point Action
Lamp Main Sub Main Sub