Connections for intrinsically safe supply of the gas flow meter
n.s. negligible small,
The values are valid as the sum for terminals Aux, 1A, 1B, 2A, 2B
Parameter
IIA IIB IIC Unit
Gas flow meter voltage supply (intrinsically safe), terminal -Vout+
U
o
16.5 16.5 16.5 V
I
o
463 463 463 mA
P
o
1.3 1.3 1.3 W
C
o
2.2 2.45 0.415 μF
L
o
0.8 0.4 0.1 mH
L
o
/R
o
148 74.4 18.6 μH/Ω
Current loop intrinsically safe power supply, terminal -Vcl+
U
o
16.5 16.5 16.5 V
I
o
89 89 89 mA
P
o
368 368 368 mW
C
o
9.8 1.9 0.2 μF
L
o
32 16 2.3 mH
Switching inputs FI.O (DI.0), FI.1 (DI.1), DO.2, DO.3 supply (intrinsically safe)
U
o
16.5 16.5 16.5 V
I
o
9.7 9.7 9.7 mA
P
o
40 40 40 mW
C
o
9.8 2.45 0.41 μF
L
o
300 200 100 mH
U
i
16.5 16.5 16.5 V
C
i
000μF
L
i
000mH
Serial interfaces RS485 supply (intrinsically safe), terminals 1A, 1B, 2A, 2B
including auxiliarxy power-
U
o
7.14 7.14 7.14 V
I
o
164 164 164 mA
P
o
293 293 293 mW
C
o
296 196 2.55 μF
L
o
52.50.33mH
U
i
7.14 7.14 7.14 V
C
i
3.45 3.45 3.45 μF
L
i
n.sn.sn.smH